17

Section 9 - Boiler Installation

Figure 7

Figure 8

(4) 12mm x 50mm studs

(4) 12mm x 50mm studs

(4) 12mm washers

(4) 12mm washers

(4) 12mm nut

(4) 12mm nut

Supply Manifold

Return Flange

Gasket

Gasket

Gasket

Diffuser

TOP OF BOILER

BOTTOM OF BOILER

Note: Threads used on the studs is metric. Any attempt to use standard (English) thread-
ed studs in place of those supplied will damage the boiler block.

!

Manifold and Diffuser Installation

1. Attach supply manifold as indicated in Fig. 7. Install return port diffuser and attach return flange as shown in Fig. 8.

NOTE: Make sure diffuser slots face upward (see Fig. 8).