Lanair MXB360 User Manual

Page 9

Advertising
background image

Visit our website at: www.lanair.com

9

Section 3 - Boiler Room Air Requirements

Figure 2

When air comes directly from outdoors, again use two openings as explained on page 8 and above except:

• Direct connection or vertical ducting allow 1 sq. inch per 4,000 BTU/HR.

• Direct connection through horizontal ducting allow 1 sq. inch per 2,000 BTU/HR

• All ducting shall be the same size as opening but no less than 3" x 3" or 9 square inches.

Remember to compensate for louver blockage when calculating free air. Refer to manufacturer's instructions or use this
general guide:

WOOD LOUVERS- Allow 20-25% free air

METAL LOUVERS OR GRILLES - Allow 60-70% free air

Any louver damper should lock open or interlock with the burner to open automatically when the boiler operates.

12" Maximum

Louvered
openings for
ventilation &
combustion

12" Maximum

Advertising