Indicators, 3) (1) logic led (green) (2) error led (red), 3) timer led (green) – IDEC FS1A Controller User Manual

Page 21: 4) input/output status led (orange)

Advertising
background image

2-12

Indicators

0 .1 .5 1 2 5

15 30

SAFE-IN

TIMER(S)

SAFE-OUT

SOLENOID
-OUT

START-IN

X0

X1

X2

X3

X4

X5

X6

X7

X10

X11

X12

X13

X14

X15

X16

X17

Y0

Y1

Y2

Y3

Y17 Y20

LOGIC ERROR

(1) Logic LED

Indication

Status

Descriptions

ON

The selected logic is in Run or Protection state.

“1”... “8”

Blink

The selected logic is in Configuration state.

“E”

Blink

The selected logic has Configuration error
(The logic is not selected or more than one logic is
selected.)

Random pattern

ON/Blink

Initializing (Initial state)

Blank

OFF

Error (stop state)

(2) Error LED

Indication

Status

Descriptions

“1”

ON

Input monitor error (Protection state)

“2”

ON

Wiring error at safety inputs or error in safety input
circuits

“3”

ON

Wiring error at start inputs or error in start input circuits

“4”

ON

Wiring error at safety outputs or error in safety output
circuits

“5”

ON

Muting lamp error (disconnection) (Logic4 only)

“6”

ON

Power supply error or internal power supply circuit error

“7”

ON

Internal error, power supply error or internal power
supply circuit error

“9”

ON

EMC disturbance

ON

Configuration procedure is in progress (Configuration
state)

“C”

Blink

Configuration is valid

Note

(Configuration state)

Random

ON/Blink

Initializing (Initial state)

Blank

OFF

Normal operation (Run state)

Note. Blinks for 1 to 5 seconds after the enter button is pressed. Releasing the button during

blinking activates the setting. The blinking LED becomes ON if the button is pressed for more
than 5 seconds, and the setting becomes invalid even after the button is released.



(1) (2)

(4)

(3)

(1) Logic LED (green)
(2) Error LED (red)

(3) Timer LED (green)

(4) Input/Output status LED (orange)

SAFE-IN

START-IN

SAFE-OUT

SOLENOID-OUT