5-15

●State monitor outputs: Y14 to Y16

Y14 to Y16 monitor outputs for the internal status of the SafetyOne.
Y14 turns ON during Initial state or Stop state.
Y15 turns ON in the Initial state, Protection state or Configuration state.
Y16 turns ON while in the Run state.
Refer to “Chapter 4 BASIC OPERATION”, or “Chapter 6 TROUBLESHOOTING”, for details of
each state.

Warning

Monitor outputs are not safety outputs. Do not use these to construct a safety system.

●Solenoid outputs: Y17 and Y20

Y17 and Y20 are outputs for solenoid control that are used for a safety switch with a lock.
In the Run state, when the safety outputs are OFF and 1 or more safety inputs are OFF, the
solenoid outputs are ON. When all safety inputs are ON, the solenoid outputs are OFF, although
the start input is not activated.

Warning

Solenoid outputs are not safety outputs. Do not use these to construct a safety system.

Caution

Refer to "Chapter 2 PRODUCT SPECIFICATIONS" for specifications of each input and output.