29 timing chart (logic 3) – IDEC FS1A Controller User Manual

Page 70

Advertising
background image

5-29

Timing chart (Logic 3)

(X2...X13 are ON in this timing chart.)

Safety input : X0

Manual start input
: X16

Safety output :
Y0,Y1,Y2,Y3

Monitor output for
X0 and X1 : Y4

Monitor output for
safety output :
Y12,Y13

RUN monitor :
Y16

Solenoid output :
Y17,Y20

Power ON

Safety output ON

Off delay

time

Safety input : X1

Safety input : X0

Control start input
: X17

Safety output :
Y0,Y1,Y2,Y3

Monitor output for
X0 and X1 : Y4

Monitor output for
safety output :
Y12,Y13

RUN monitor :
Y16

Solenoid output :
Y17,Y20

Power ON

Safety output ON

Off delay

time

Safety input : X1

0.1s...5s

1.Using the manual start input (X16)

2.Using the control start input (X17)

Max. 6s

Max. 6s

Note

Note

Note:

When the input time difference at the dual channel solid state inputs (X0-X1 and X2-X3) is 0.1s or more,
an input monitor error is detected .
When the input time difference at the dual channel direct opening inputs

(X4-X5, X6-X7, X10-X11, and X12-X13) is 0.5s or more,

an input monitor error is detected.
Refer to “Logic functions” for details.

Note

Max. 0.1s

Min. 0.1s

Note

Max. 0.1s

(X2...X13 are ON in this timing chart.)

Initialization

Initialization