3.6.6. Testing a Three Phase Transformer Using Auto Detect Mode

The ATRT-03 provides a convenient Auto Detect mode that can automatically detect 130
specific vector groups for different transformer types defined by ANSI, CEI/IEC, and Australian
standards. The transformer configurations supported are listed in Appendix B, C, and D. The
ATRT-03 can detect the vector diagrams for Delta-Delta, Wye-Wye, Delta-Wye, and Wye-Delta
transformer types. Follow the steps below to test a three phase transformer using the auto
detect mode:

a. Start from the “START-UP” menu:

Press the

[4]

key (DIAG).

b. The following screen will be displayed:

Press the

[3]

key (AUTO-DETECT XFMR).

c. The following screen will be displayed:

Select a supported three phase transformer type by pressing the corresponding numeric
key on the keypad (

[1]

,

[2]

,

[3]

, or

[4]

). For this example, we will perform a Y-dT test

(option 2).

d. The following screen will be displayed:

Press the

[START]

key.

Y-dT AUTO DETECT

“START” TO INITIATE

ENTER XFMR TYPE:
1.dT-Y 2.Y-dT
3.Y-Y 4.dT-dT

1.CABLE TEST
2.VERIFICATION TEST
3.AUTO-DETECT XFMR

1.TEST XFMR 08/23/10
2.SETUP 08:25:15
3.CALCULATOR

4.DIAG 5.QUICK TST