Gas pressure checks, Gas control valve, Fig. 17 – L.B. White I-34 Infraconic Spark Ignition User Manual

Page 18: Fig. 16

Advertising
background image

FUEL SUPPLY VALVEG

(OPEN THIS VALVE TO USEG

PRESSURE GAUGE)

G

TEST KIT HOSE

PRESSURE GAUGE KITG
20736

GAS SUPPLY HOSE

GAS CONTROL VALVE

OPEN

G

1177

FIG. 17

GAS PRESSURE CHECKS

AA.. PPrreeppaarraattiioonn

1. Obtain an L.B. White pressure gauge test kit -

Part # 20736.

2. Disconnect the heater from the electrical supply and

close the fuel supply valve to the heater.

3. Brush or blow off any dust and dirt on or in the vicinity

of the gas control valve.

4. Disconnect the gas hose from the heater.

BB.. GGaauuggee IInnssttaallllaattiioonn

1. Connect the pressure test kit between the heater and

gas supply hose. See Fig. 17. Insure both gas shut-

off valves on the test kit are in the closed position

when connecting the kit to the heater and gas supply.

2. Reconnect the heater to its electrical supply and open

the main fuel supply valve to the heater.

3. Open only the gas shut-off on the test kit which is

connected to gas supply.

4. Light the heater.

CC.. RReeaaddiinngg PPrreessssuurreess

1. With the heater operating, the pressure gauge should

read the pressure specified on the dataplate.

2. Does the reading on the gauge of the test kit agree

with that specified on the dataplate? If so, then no

further checking or adjustment is required. Proceed

to Section D.

3. If the pressure does not agree with that specified on

the dataplate, then the regulator controlling gas

pressure to the heaters requires adjustment.

DD.. CCoom

mpplleettiioonn

1. Once gas pressure has been confirmed and/or

properly set, close the fuel supply valve to the heater

and allow the heater to burn off any gas remaining in

the gas supply hose.

2. Disconnect the heater from its electrical supply.

3. Remove the gauge kit and reconnect the gas hose

and electrical supply to the heater. Tighten securely.

4. Open the fuel supply valves and set building

controller to desired temperature.

ADAPTER

INLET

BUSHING

GROUND LEAD

VALVE GROUNDING ANDG
ATTACHMENT SCREW

INJECTOR G
BODY

ADAPTER

GAS CONTROL G
VALVE

GAS CONTROL VALVE

1. Brush or blow off any dust in vicinity of gas control

valve.

2. Disconnect the gas hose and remove control box

cover.

3. Loosen water tight connector nut at the control box

for the power supply leads of the control valve.

4. Disconnect the valve’s electrical leads from the

ignition module.

5. Remove the connector nut from the valve leads.

6. Loosen the valve ground and attachment screw at the

injector body.

7. Remove bushing with hose adapter from control valve

inlet. See Fig. 16.

8. Secure the gas valve adapter at the outlet of the gas

control. Remove the control valve from adapter.

FIG. 16