Diagnostics and troubleshooting – Pinnacle Systems SLT Series User Manual

Page 22

Advertising
background image

15

SLT Series

Diagnostics and Troubleshooting

c) Slave has legally overridden the

Master because it believed the

current conditions require the

relays to be off.

d) Line voltage levels too low to

activate either relay.

Cure(s):

Only reason a) can be checked by user,

all other reasons can only be checked

by authorized trained personnel.

7 ...................... Auto Blank Activated

Definition:

The Auto Blank keyswitch was moved

from the OFF/RESET position into an

Auto Blank position and an object

covering a total of less then nine beams

was found. Before Code 7 is displayed,

the display will show the exact number

of blocked beams for about two

seconds (see Auto Blank section under

Optional Features, Page 5).

Status:

GREEN light on, relays closed.

Reason(s):

An obstruction was placed in the field

of view of the light curtain and was

subsequently programmed into the

computer via the keyswitch.

Cure(s):

To deactivate the Auto Blank, turn the

keyswitch back into the OFF/RESET

position or power down the light curtain

to clear the memory.

8 ...................... Auto Blank Obstruction Missing

Definition:

After Auto Blank was activated, the

obstruction was moved from its initial

position in the guarded area or the

obstruction was too big.

Status:

GREEN in Auto Fixed Blank mode
RED in the other two Auto Blank modes

(see Auto Blank section under Optional

Features, Page 5).

Reason(s):

a) The user activated the Auto Blank

and subsequently moved the

obstruction from its programmed

position.

b) The total obstruction size exceeded

eight beams.

Cure(s):

a) Re-adjust the obstruction position

and stabilize its movement.

b) Make sure the total size does not

exceed eight beams.

9 ...................... Internal Ram Fault

Definition:

When the light curtain self-tests, it

exercises all of its internal ram locations

to make sure that they all store data

properly. Upon testing, one or more

memory locations failed this test.

Status:

RED light, fail safe relays open.

Reason(s):

a) Reset circuitry failed to respond to

a glitch in the power supply line.

b) Bad ram.
c) Bad ground.

Cure(s):

Check grounds, power down the light

curtain for one minute and try again. If

this does not work, the unit must be

serviced by authorized personnel.

A ...................... Master cannot talk to slave computer

Definition:

The Master waits for the Slave to

communicate between each scan of the

light curtain and will time-out if it can’t

complete its communication.

Status:

RED light, fail safe relays open.

Reason(s):

a) Faulty microprocessor chip(s).
b) Noise on power line causes one of

the two microprocessors to reset

and fall out of sync with the other.

c) Intermittent drop in line voltage.

Cure(s):

If the problem is intermittent, then it is

noise. Tap power for the Receiver Pylon

head of all other devices that cause

noise (i.e., solenoids, motors) so that it

gets cleaner power. Also, monitor line

voltage for any intermittent drops.

B ...................... Data disagreement with the slave

unit

Definition:

The Master has linked up with the slave

properly, but the Slave sees dif ferent

data then the Master.

14