Diagnostics and Troubleshooting

Status:

RED light, fail safe relays open.

Reason(s):

a) information on switch positions

differ.

b) values of special registers differ.

Cure(s):

Check ground connections. The unit

must be serviced by authorized

personnel.

C ...................... External infrared source detected at

startup

Definition:

Infrared signals detected when the right

side Emitter Pylon was not signaled to

transmit.

Status:

RED light, fail safe relays open.

Reason(s):

External pulse of infrared light from a

strobe or another light curtain was

detected during self-testing.

Cure(s):

Turn off all other light curt ains in the

entire area and try the curtain again. It

is probably another nearby light curtain

emitter throwing this light curtain out of

sync. You may need to reverse their

position by exchanging the Receiver

and Emitter pylon with each other so it

fires its beams in the other direction.

D ...................... Internal Short/Open

Definition:

Between each scan the Master looks

at the output of each receiver circuit in

turn. Should an improper signal level

occur, this code is displayed.

Status:

RED light, fail safe, relays open.

Reason(s):

a) Problem in any one of the cable

connections inside the Receiver

Pylon.

b) Short in one of the phototransistors.
c) Open in one of the comparators.
d) External infrared source of long

duration.

e) Beam in transmitter pylon left on.

Cure(s):

Check all cables inside the Receiver

Pylon for bent pins or cold solder joints.

E ...................... Beam and/or board select line failure

Definition:

The Master has linked up with the slave

properly, but the Slave sees dif ferent

data then the Master.

Status:

RED light, fail safe relays open.

Reason(s):

a) Board select chip bad.
b) Beam select chip bad.
c) Master has problem with data port

select lines.

d) Slave has problem with reading

select lines.

e) Short or open on PCB.

Cure(s):

Check ground connections. The unit

must be serviced by authorized

personnel.

F ...................... Clock/Code Failure

Definition:

The onboard watchdog timer sensed a

clock malfunction or a failure in the

execution of the code. Upon initial

power up, the Diagnostic Display should

count backwards from ‘.F .’ to ‘.0.’ to

indicate that its clock is running. If you

do not see this happening when

powering up, the clock or computer chip

is bad. If you see it happen and then

get this code, a glitch has caused a

software code failure.

Status:

RED light, fail safe relays open.

Reason(s):

a) Voltage levels too low for operation.
b) Crystal bad.
c) Power surge caused code to

executed improperly.

d) Reset circuit glitch.
e) Computer bad.

Cure(s):

Check for low line voltage. If the line

voltage drops below 105VAC (even for

just a second) the guard could lock up

and display this code.