Outside combustion air supply, Air for combustion (residential), Electrical service installation – Enerco HST45 User Manual

Page 16: Direct outside air for combustion (residential), System requirements

Advertising
background image

16

| Gas-Fired Low-Intensity Infrar ed Heater

Operating Instructions and Owner’s Manual

Non-Pressurized Outside Air Supply Duct

Outside Combustion Air Supply

The MHT / HST tube heater is approved for installation with an outside air
supply system. Some compounds such as halogenated hydrocarbons
or other corrosive chemicals in the air can be drawn into the
equipment and cause an accelerated rate of corrosion of some of the
heater components. The use of such chemical compounds near the
enclosure should be avoided.

IMPORTANT: If the building has a slight negative pressure or
contaminants are present in the air, an outside combustion air
supply to the heaters is strongly recommended.
For an outside air supply a three (3") inch O.D. single wall pipe may
be attached to the heater. The duct may be up to twenty five (25')
feet maximum length or two (2') feet minimum length with no
more than two (2) elbows.

The air supply duct may have to be insulated to prevent
condensation on the outer surface. The outside air terminal should
be securely fastened to the outside wall by drilling four (4) holes in
the outside flange; wood screws or bolts and expansion sleeves
may be used to fasten terminal.

VERTICAL THROUGH THE ROOF

Intake Vent

3" Starting Collar

¼” per ft.
downwards

6" Min.

3" Dia.

Single-Wall Pipe

Flashing

3' Min.

Vent Cap
(Leslie VersaCap)

Vertical Venting

Air For Combustion (Residential)

If indoor combustion air is to be supplied for a tightly enclosed
area, one square inch of free area opening shall be provided below
the heater for each 1,000 Btu/hr of heater input.

When outside air is used, the opening below the heater shall be
one square inch of free area for each 4,000 Btu/hr of heater input.
In contaminated atmospheres or high humidity areas, optional
outside air for combustion is recommended.

Adequate clearances around the perforated fresh air plate must be
maintained at all times. In larger open areas of buildings,
infiltration normally is adequate to provide air for combustion.

Direct Outside Air For Combustion (Residential)

Outside combustion air should be supplied directly to the heater
when the building is subject to negative pressure or contaminants
are present in the building air. These contaminates include paints,
solvents, corrosive vapors or any other foreign particles that may
cause damage to the heater or result in poor combustion.

Outside combustion air can be brought directly to the heater by a 3
inch diameter duct less than 25 feet long or equivalent. This is
attached to a 3 inch starting collar that is fitted on inlet side of the
control cabinet. An approved vent cap must be placed directly to the
end of the outside combustion air inlet pipe. The combustion air inlet
should be a minimum of 3 feet, either vertically or horizontally, from
the flue vent termination. The air intake terminal must be located not
less than one foot above grade. It is good installation practice to
supply combustion air from the same pressure zone as the vent
outlet.
In colder climates, where necessary, insulate the fresh air duct. Avoid
locating the fresh air duct directly above the control box. Provide a
capped cleanout T as necessary.

Enerco Group, Inc.,

Electrical Service Installation:

System Requirements

The MHT / HST tube heater requires a grounded three-prong electrical
outlet to be installed within 18”of the rear surface of the heater’s
burner box. It is recommended that the outlet for the heater be
ceiling-mounted and should be on a dedicated circuit. DO NOT use
an electrical extension cord to operate the heater.

In order to control the heater thermostatically, it is necessary that
the grounded three-prong electrical outlet be controlled with a on/
off switch or a line voltage thermostat. Please consult with an
electrician or follow all local electrical codes.

Heater Rating: 120 VAC, 60Hz, Single Phase, 1 Amp