Power Supply Concept

Notes on power cabling

Single basic unit with two UPSs

Figure 73: Single basic unit with two UPSs

If you need higher availibility, you can connect a single BX600 S3 basic unit to
two UPS devices. In this case you must take into account that each UPS must
provide approximately 5120 Watts to power the basic unit, even if the mains
supply and one UPS were to fail.

UPS

UPS

Single-phase
or
3-phase input