6. Wire Power to the Compact FieldPoint System

Each cFP-20xx on your network requires an 11–30 VDC power supply.

1. Connect the positive lead of the primary

power supply to one of the V1 terminals
and the negative lead to one of the
C terminals.

2. If you are using a backup power supply,

connect the positive lead to V2 and the
negative lead to one of the C terminals.
The cFP-20xx uses the power supply
with the higher voltage level. V2 is
isolated from the other V terminals.

3. Refer to the operating instructions for the power requirements of each I/O

module.

4. Use a separate power supply for each module that needs external power.

Caution

Cascading power defeats isolation between the cascaded

modules.