Power requirement, Physical characteristics, Environmental – National Instruments cFP-20xx User Manual

Page 19

Advertising
background image

© National Instruments Corporation

19

cFP-20xx Quick Start Guide

Power Requirement

Power supply range........................... 11 to 30 VDC

Recommended power supply

cFP-BP-4 system ........................ 15 W
cFP-BP-8 system ........................ 20 W

Power consumption

cFP-2000 .................................... 4.8 W + 1.1(I/O module power

requirements)

cFP-2010 .................................... 5.0 W + 1.1(I/O module power

requirements)

cFP-2020 .................................... 6.1 W + 1.1(I/O module power

requirements)

Physical Characteristics

Screw-terminal wiring ...................... 16–26 AWG copper conductor wire with

7 mm (0.28 in.) of insulation stripped from
the end

Torque for screw terminals ............... 0.5–0.6 N · m (4.4–5.3 lb · in.)

Weight of cFP-20xx .......................... 278 g (9.8 oz)

Environmental

FieldPoint modules are intended for indoor use only. For outdoor use, they must
be installed in a suitable sealed enclosure.

Operating temperature ...................... –25 to 60 °C

Storage temperature .......................... –40 to 85 °C

Advertising