Gpctr1_out signal, Figure 4-36. gpctr1_out signal timing, Gpctr1_up_down signal – National Instruments AT E Series User Manual

Page 95: Gpctr1_out signal -48 gpctr1_up_down signal -48

Advertising
background image

Chapter 4

Connecting Signals

AT E Series User Manual

4-48

ni.com

As an output, the GPCTR1_GATE signal monitors the actual gate signal
connected to general-purpose counter 1, even if the gate is being externally
generated by another PFI. This output is set to high-impedance at startup.

Figure 4-35 shows the timing requirements for the GPCTR1_GATE signal.

Figure 4-35. GPCTR1_GATE Signal Timing in Edge-Detection Mode

GPCTR1_OUT Signal

This signal is available only as an output on the GPCTR1_OUT pin. The
GPCTR1_OUT signal monitors the TC device general-purpose counter 1.
You have two software-selectable output options—pulse on TC and toggle
output polarity on TC. The output polarity is software selectable for both
options. This output is set to high-impedance at startup. Figure 4-36 shows
the timing requirements for the GPCTR1_OUT signal.

Figure 4-36. GPCTR1_OUT Signal Timing

GPCTR1_UP_DOWN Signal

This signal can be externally input on the DIO7 pin and is not available as
an output on the I/O connector. General-purpose counter 1 counts down
when this pin is at a logic low and counts up at a logic high. This input can
be disabled so that software can control the up-down functionality and

Rising-Edge

Polarity

Falling-Edge

Polarity

t

w

= 10 ns minimum

t

w

GPCTR1_SOURCE

GPCTR1_OUT

GPCTR1_OUT

(Toggle Output on TC)

(Pulse on TC)

TC

Advertising