Table GD-2— General Data — 35-40 Ton

35 Ton

40 Ton

Cooling Performance

1

Nominal Gross Capacity

417,000

513,000

Natural Gas Heat

2

Low

High

Low

High

Heating Input (BTUH)

350,000

600,000

400,000

800,000

First Stage

250,000

425,000

300,000

600,000

Heating Output (BTUH)

283,500

486,000

324,000

648,000

First Stage

202,500

344,500

243,000

486,000

Steady State Efficiency (%)

3

81.00

81.00

81.00

81.00

No. Burners

1

2

1

2

No. Stages

2

2

2

2

Gas Connection Pipe Size (in.)

3

/

4

1

3

/

4

1

Electric Heat
KW Range

5

27-90

41-108

Capacity Steps:

2

2

Compressor
Number/Type

2/Scroll

3/Scroll

Size (nominal)

15

15/15/10

Unit Capacity Steps (%)

100/50

100/60/40

Motor RPM

3450

3450

Outdoor Coil — Type

Lanced

Lanced

Tube Size (in.) OD

3

/

8

3

/

8

Face Area

51.33

69.79

Rows/Fins Per Inch

2/16

2/16

Indoor Coil — Type

Hi-Performance

Hi-Performance

Tube Size (in.) OD

1

/

2

1

/

2

Face Area (sq. ft.)

31.67

37.50

Rows/Fins Per Foot

3/180

3/180

Refrigerant Control

TXV

TXV

No. of Circuits

1

2

Drain Connection No./Size (in)

1/1.25

1/1.25

Type

PVC

PVC

Outdoor Fan Type

Propeller

Propeller

No. Used/Diameter

3/28.00

4/28.00

Drive Type/No. Speeds

Direct/1

Direct/1

CFM

24,800

31,700

No. Motors/HP/RPM

3/1.10/1125

4/1.10/1125

Indoor Fan Type

FC

FC

No. Used

1

1

Diameter/Width (in)

22.38/22.00

25.00/25.00

Drive Type/No. Speeds

Belt/1

Belt/1

No. Motors/HP

1/7.50/10.00/15.00

1/10.00/15.00

Motor RPM

1760

1760

Motor Frame Size

213/215/254T

215/254T

Exhaust Fan Type

Propeller

Propeller

No. Used/Diameter (in)

2/26.00

2/26.00

Drive Type/No. Speeds/Motors

Direct/2/2

Direct/2/2

Motor HP/RPM

1.0/1075

1.0/1075

Motor Frame Size

48

48

Filters — Type Furnished

Throwaway

Throwaway

No./Recommended Size (in)

6

16/16 x 20 x 2

17/16 x 20 x 2

Refrigerant Charge (Lbs of R-22)

4

51.50

26.00/47.10 per circuit

Minimum Outside Air Temperature
For Mechanical Cooling

0 F

0 F

Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. Rated and tested

in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93.

2. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.

Ratings shown are for elevations up to 4,500 feet.

3. Steady State Efficiency is rated in accordance with DOE test procedures.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Maximum KW @ 208V = 41, @ 240V = 54.
6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit Installation, Operation, Maintenance Guide.