50 ton, Outdoor air damper leakage, Erformance adjustment factors – Trane RT-PRC007-EN User Manual

Page 17: General data

Advertising
background image

17

RT-PRC007-EN

General Data

50 Ton

Cooling Performance

1

Nominal Gross Capacity

616,000

Natural Gas Heat

2

Low

High

Heating Input (BTUH)

400,000

800,000

First Stage

300,000

600,000

Heating Output (BTUH)

324,000

648,000

First Stage

243,000

486,000

Steady State Efficiency (%)

3

81.00

81.00

No. Burners

1

2

No. Stages

2

2

Gas Connection Pipe Size (in.)

3

/

4

1

Electric Heat
KW Range

5

41-108

Capacity Steps:

2

Compressor
Number/Type

3/Scroll

Size (nominal)

14

Unit Capacity Steps (%)

100/67/33

Motor RPM

3450

Outdoor Coil — Type

Lanced

Tube Size (in.) OD

3

/

8

Face Area (sq. ft.)

69.79

Rows/Fins Per Inch

2/16

Indoor Coil — Type

Hi-Performance

Tube Size (in.) OD

1

/

2

Face Area (sq. ft.)

37.50

Rows/Fins Per Foot

4/164

Refrigerant Control

TXV

No. of Circuits

2

Drain Connection No./Size (in)

1/1.25

Type

PVC

Outdoor Fan Type

Propeller

No. Used/Diameter

4/28.00

Drive Type/No. Speeds

Direct/1

CFM

31,700

No. Motors/HP/RPM

4/1.10/1125

Indoor Fan Type

FC

No. Used

1

Diameter/Width (in)

25.00/25.00

Drive Type/No. Speeds

Belt/1

No. Motors/HP

1/10.00/15.00/20.00

Motor RPM

1760

Motor Frame Size

215/254/256T

Exhaust Fan Type

Propeller

No. Used/Diameter (in)

2/26.00

Drive Type/No. Speeds/Motors

Direct/2/2

Motor HP/RPM

1.0/1075

Motor Frame Size

48

Filters — Type Furnished

Throwaway

No./Recommended Size (in)

6

17/16 x 20 x 2

Refrigerant Charge (Lbs of R-22)

4

25.70/54.30 per circuit

Minimum Outside Air Temperature
For Mechanical Cooling

0 F

Table GD-3— General Data — 50 Ton

Table GD-4 — Economizer Outdoor Air
Damper Leakage (Of Rated Airflow)

Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does

not include the effect of fan motor heat. Rated and tested in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.

2. Heating Performance limit settings and rating data were established and approved under laboratory test conditions

using American National Standards Institute standards. Ratings shown are for elevations up to 4,500 feet.

3. Steady State Efficiency is rated in accordance with DOE test procedures.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Maximum KW @ 208V = 41, @ 240V = 54.
6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit Installation, Operation,

Maintenance Guide.

P Across Dampers (In. WC)

0.5 (In.)

1.0 (In.)

Standard

1.5 %

2.5 %

Optional “Low Leak”

0.5 %

1.0 %

Note: Above data based on tests completed in
accordance with AMCA Standard 575.