Water piping — multiple zones, Gold cga gas-fired water boiler — boiler manual – Weil-McLain Gold CGa User Manual

Page 19

Advertising
background image

Part Number 550-101-009/0107

19

GOLD CGa Gas-Fired Water Boiler — Boiler Manual

Figure 11

Zoning with circulators — return water

130°F or higher.

Figure 12

Zoning with zone valves — return water

130°F or higher.

1

Boiler isolation (balancing)

valves

2

Flow/check valve

3

System or zone circulator

5

Zone valve

6

Drain valve

9

Relief valve

10

Automatic air vent (with diaphragm-type expansion tank), or connect

to tank fitting (closed-type expansion tank).

DO NOT

use an automatic

air vent when using closed-type expansion tank. It would allow air to

leave the system, causing waterlogging of the expansion tank.

11

Fill valve

12

Diaphragm-type or bladder-type expansion tank, if used (For closed-

type expansion tank, pipe from top of air separator to tank fitting as in

Figure 10

, page 1.)

13

Air separator and automatic vent, if used (Note that the fill valve must

always be connected to the expansion tank, regardless of location of

expansion tank circulator or air separator.

For systems with possible low return-water temperature (such as converted gravity systems,

radiant heating systems and heat pump systems), refer to the special piping suggestions of

Figures 13 – 17

, as applies. Failure to prevent sustained low return water temperature to

the boiler could cause corrosion of the boiler sections, resulting in severe personal injury,

death or substantial property damage.

Water piping — multiple zones

(continued)