Water piping — refrigeration systems, Piping — low temperature systems – Weil-McLain Gold CGa User Manual

Page 25

Advertising
background image

Part Number 550-101-009/0107

5

GOLD CGa Gas-Fired Water Boiler — Boiler Manual

3 System or zone circulator

7 System temperature valves (see instructions to the left for

adjusting valves)

8 Blend temperature gauge

9 Relief valve

10 Automatic air vent (with diaphragm-type expansion

tank), or connect to tank fitting (closed-type expansion
tank). DO NOT

use an automatic air vent when using

closed-type expansion tank. It would allow air to leave
the system, causing waterlogging of the expansion tank.

11 Fill valve

12 Diaphragm-type or bladder-type expansion tank, if used

(For closed-type expansion tank, pipe from top of air
separator to tank fitting as in Figure 10

, page 1

.)

Figure 17

System-bypass piping — Zoning with

zone valve or circulators, return water

130°F or higher — (Alternative to boiler-

bypass piping

Figures 15 and 16,

page 23)

Figure 18 Piping refrigeration systems

Prevent chilled water from

entering boiler

Water piping — refrigeration systems

3e

Install boiler so that chilled medium is piped in parallel
with the heating boiler. Use appropriate valves to prevent
chilled medium from entering boiler. See Figure 18 for
typical installation of balancing valve and check valve.

If boiler is connected to heating coils located in air han-
dling units where they can be exposed to refrigerated
air, use flow control valves or other automatic means to
prevent gravity circulation during cooling cycle.

Piping — low temperature systems

(continued)

3d