– Electrical Installation

4.0 Electrical Installation


Please see the Quick Start Guide for UL Class 1 Division 2 installation instructions.

4.1 Wiring

4.1.1 Terminal Block

Both power and data signals are connected to the terminal block. Figure 4-1 shows the
layout.

Operating Voltage

10 to 20 VDC

Maximum Surrounding Ambient Air Temp

74°C

Wiring Terminals

Use Copper Wire Only, One Conductor Per Terminal

Wire Range

30 to 12 AWG

Tightening Torque

0.5 to 0.6 Nm

Temperature Rating of Field Installed Conductors

105°C minimum, sized for 60°C ampacity.

Figure 4-1

Terminal Block

4.1.2 Power Supply Connections

The radio modem requires power from an external source. The radio modem requires 10
to 30 VDC. Power use depends on the model:

ZXT9RM

– 1.7 Watts typical, 5.8 Watts maximum.

ZXT24RM

– 1.2 Watts typical, 3.5 Watts maximum.


Connect the positive and negative power leads to the Power In(+) and Power In (-)
terminals on the terminal block.


.