Appendix C: Operation without a Controller -
Alarm Wiring
Each CPS3200U Shelf Provides Alarm contact closures for Power Major and Power Minor for operation without a
controller. Wire these relays into the alarm network in deployments where a controller is not utilized. If a controller is
installed then an alarm cable can be attached to the QS941A controller during final installation in section 8 under
“Installing the QS941A Ethernet Module”.
Step
Action
1.
Attach the required alarm leads to the office alarm screw terminals (TB1 on the alarm card) as
designated.
Figure 44 Alarm Card Office Alarm Pinout and Shelf ID
Figure 45 Alarm Card Office Alarm Cables
2.
Set Shelf ID to address 0, 0 - Figure 44.
3.
Reinstall Alarm card and close distribution door.
Office Alarm Cables
Shelf ID Switches