Parameters – Elmo Rietschle 2FC4...-1CB User Manual
Page 42
7
Parameters
610.00260.40.000 · 05.2014
42
/
74
© Gardner Denver Deutschland GmbH
1,130
Setpoint source
Unit: integer
Relationship to
parameter:
3,062 – 3,069
Parameter HB:
S. xy
Transfer
status:
2
min: 0
Intrinsic value
(to be en-
tered!)
max: 10
Def: 1
Specifies the source from which the setpoint is to be read.
0 = internal potentiometer
1 = analogue input 1
2 = analogue input 2
3 = MANUAL CONTROL UNIT MMI/PC
4 = SAS
6 = motor potentiometer
7 = total analogue inputs 1 and 2
8 = PID fixed setpoints (3,062 - 3,069)
9 = fieldbus
10 = integrated soft PLC
1,131
Software release
Unit: integer
Relationship to
parameter:
1,132
1,150
2,050
4,030
4,050
Parameter HB:
S. xy
Transfer
status:
2
min: 0
Intrinsic value
(to be en-
tered!)
max: 13
Def: 0
WARNING! Depending on the change made, the motor
may start to run directly.
Selection of the source for the control release.
0 = digital input 1
1 = digital input 2
2 = digital input 3
3 = digital input 4
4 = analogue input 1 (must be selected in parameter 4,030)
5 = analogue input 2 (must be selected in parameter 4,050)
6 = field bus
7 = SAS
8 = digital input 1 right / digital input 2 left
1,150 must be set to "0"
9 = autostart
10 = integrated soft - PLC
11 = fixed frequency inputs (all inputs that have been selected in
parameter 2,050)
12 = internal potentiometer
13 = membrane keyboard (start & stop buttons)
If the hardware release and a setpoint are applied, the motor
may start to run directly!
This cannot be prevented even with parameter 1,132.