2. Installation

2.12 Auxiliary interconnections between UPS units in parallel configurations

Redundant parallel configuration (maximum two UPS units)

For security reasons, the connections of the auxiliary interconnections of the parallel UPSs must be carried out

whilst all the UPSs are de-energised.

Exchange-current interconnections
Link connectors XMS02 and XMS03 on the

two UPS units.

CAN // interconnections:
Fit a blue plug on connector XMS06 on

UPS1.

Link connector XMS07 on UPS1 to connector
XMS06 on UPS2.

Fit a red plug on connector XMS07 on U PS2.

Note. The supplied cables (10 m) limit the

distance between the two UPS units to
approximately six meters.

XMS02 XMS03

XMS06 XMS07

XMS04 XMS05

CAN //

XMS02 XMS03

XMS06 XMS07

XMS04 XMS05

CAN //

10

10

12

12

10

10

12

12

UPS 1

UPS 2

Blue
plug

Red plug