2. Installation

Parallel UPS

Parallel-connection cables for connection to

the external bypass cabinet (not supplied
max. 2.5 mm

2

). The CAN and I exchange

cables are supplied.

Relay communication card

Optional communications cards

Ties

General-shutdown cable (not supplied, max.

2.5 mm

2

) and external battery circuit breaker

cable must be tied down separately

Ties

Cable description

Insulation level

Location on illustration

External bypass cabinet cable

ELV

1

CAN cables

SELV

1

Exchange-current cables

SELV

1

Relay communication card

SELV or LV

3

Optional communication card

SELV

4

General-shutdown cable

SELV

6

External battery circuit-breaker cables

SELV

7

To ensure sufficient isolation of exchange-current, CAN and external bypass cabinet cables, they must be run

separately from the power cables. Reinforce the insulation of these control and communication cables if any risk of
contact with the power cables subsists.