48

TABLE 31

MULTI-FUNCTION OUTPUT RELAY CONTACTS PROGRAMMING

Function No.

Code

8.00: Multi-Function Output Relay 1

0000: Run
0001: Fault
0002: Target Frequency
0003: Frequency Threshold Level (> 8.04 – 8.05)
0004: Frequency Threshold Level (< 8.04 + 8.05)
0005: I

2

t or I•t Fault

0006: Load Loss
0007: External Fault
0008: Motor Overload

8.01: Multi-Function Output Relay 2

0000: Run
0001: Fault
0002: Target Frequency
0003: Frequency Threshold Level (> 8.04 – 8.05)
0004: Frequency Threshold Level (< 8.04 + 8.05)
0005: I

2

t or I•t Fault

0006: Load Loss
0007: External Fault
0008: Motor Overload


FIGURE 39

MULTI-FUNCTION OUTPUT RELAYS CONTACT CONNECTIONS




A12. MULTI-FUNCTION OPEN COLLECTOR OUTPUTS

Two Open Collector Outputs are provided, which can be programmed for Run, Fault, Target Frequency,
Frequency Threshold Level (> 8.04 – 8.05), Frequency Threshold Level (< 8.04 + 8.05), I

2

t or I•t Fault, Load

Loss, External Fault, and Motor Overload. See Table 32, on page 49, for drive programming. See Figure 40,
on page 49, for connections. See Table 33, on page 49, for the Multi-Function Open Collector Output
Electrical Ratings. See Figure 41, on page 49, for a typical application for the Open Collector Output.

Multi-Function Open Collector Output "1":
Factory programmed to operate as a Target Frequency
indicator (Function No. 8.02 set to "0002" (factory setting)). TB1 Terminal "11" is the Collector and Terminal
"12" is the Emitter (internal circuit common).

Multi-Function Open Collector Output "2": Factory programmed to operate as a Frequency Threshold
Level (< 8.04 + 8.05) indicator (Function No. 8.03 set to "0004" (factory setting)). TB1 Terminal "13" is the
Collector and Terminal "14" is the Emitter (internal circuit common).