<4. Diagnostics>

4-10

IM 01C25T01-06EN

NOTE

When setting ILBD parameters in the transmitter

via “Online Parameter” of the EJX HART 5

DTM based on FDT1.2 menu, Diag Mode

automatically changes to 0 (Stop). After the

setting, Diag Mode automatically returns to the

original value.

NOTE

When setting ILBD parameters in the transmitter

via “Download to device” of the EJX HART 5

DTM based on FDT1.2 menu, Diag Mode

automatically changes to 0 (Stop).

Diag Period

The values such as

Ratio fDP and BlkF are

averaged based on several hundreds of pressure

fluctuation values in constant time.

Diag Period

defines the sampling time is. The default value at

the shipment is set to 180 seconds.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Diag/Service

→ Diag Parameters → ILBD

Parameters → Configuration →

Diag Period →

EJX_HART 5[1.2]

DTM

Diag and Service → Advanced Diag

Configurations → Impulse Line

Blockage Detection → Diag Period

For the information on how to change the sampling

period, refer to subsection 4.2.2.10.

Diag Supp Count

When the value as

Ratio fDP or BlkF exceeds

the threshold value for several times in a row,

it is estimated that the impulse line is plugged.

Diag Supp Count defines the number of times to

estimate blockage detection.

• Procedure to call up the display

DD and DTM

(excluding EJX_

HART 5[1.2])

[Root Menu] → Diag/Service

→ Diag Parameters → ILBD

Parameters → Configuration →

Diag Supp Count →

EJX_HART 5[1.2]

DTM

Diag and Service → Advanced Diag

Configurations → Impulse Line

Blockage Detection → Threshold →

Diag Suppress Count →

If

Diag Supp Count is set to three times, an

alarm is not generated at part ‘A’ in Figure 4.4.

Because the first and second values only exceeded

consecutively the threshold.
When the value exceeds consecutively the

threshold value three times, an alarm is generated

(see part ‘B’ in Figure 4.4).

B

A

A

A

B

B

B

A

F0406.ai

Diag Supp Count (Number of times: 3)

Diag Supp Count (Number of times: 3)

Diag Period

Diag Period

Upper Threshold

(Ex.

Lim fDPmax)

Lower Threshold

(Ex.

Lim fDPmin)

An alarm is generated.

An alarm is generated.

Time

Time

Figure 4.4

Relationship of Diag Supp Count and

Alarm

The number of detection to give an alarm is set for

each blockage detection function. The default value

at the shipment is set to three times.
If fluctuating around the threshold value, an alarm

may be often generated. In this case, change the

threshold value (Limit parameter) or the sampling

time (

Diag Period) to enhance the accuracy of the

blockage detection. Refer to subsection 4.2.2.10.