Vfd high speed control, Ventilation control, Important – Mammoth 800 to 5500 CFM: Dedicated Outdoor Air System with Enthalpy Wheels (VHC) User Manual

Page 28

Advertising
background image

MAMM-VHC-IOM-1A (JANUARY 2013)

28

VFD High Speed Control

High speed fan control can be achieved by connecting dry

contact controls to the field wired (FW) terminals 374 and

375 for the supply fan and 376 and 377 for the exhaust fan.

Only VFD units have the high speed option. These controls

could also be the following: DPST switch, dehumidistat,

CO

2

sensor, light sensor, heat sensor, timer, Building Man-

agement System, etc.

CO

2

Ventilation Control

VHCs can be directly controlled by a CO

2

controller (acces-

sory or field supplied) that can be connected to the supply

and exhaust high speed contact terminals (VFD units only).

As the CO

2

levels exceed acceptable limits, dry contacts

close raising high speed fan ventilation. See Figure F5.

Alternatively a field supplied CO

2

controller output can be

connected to the BMS which can then be connected to the

supply and exhaust fan modulating signal input terminals

(VFD units only). As the CO

2

levels rise and fall the BMS

must modulate the signal to the supply and exhaust fans to

change the ventilation rate proportionally. See

Appendix G

.

The minimum VFD speed is factory default set to 40 Hertz.

301

302

304

305

305

306

307

308

320

321

322

323

324

325

326

327

328

329

UNOCCUPIED

RECIRCULATION

CONTACT (OPTIONAL)

CR

Figure F3: Unoccupied recirculation for electro-mechanical

controls (EMC) units

301

302

304

305

305

306

307

308

320

321

322

323

324

325

374

375

376

377

CR

CR

CR

OCCUPANCY

CONTACT

SUPPLY BLOWER

HIGH SPEED CONTACT

EXHAUST BLOWER

HIGH SPEED CONTACT

Figure F4: VFD high speed control

301

302

304

305

305

306

307

308

320

321

322

323

324

325

374

375

376

377

HIGH SPEED

CONTROL (SUPPLY BLOWER)

HIGH SPEED

CONTROL

RELAY CR1

OCCUPANCY

CONTACT

CR

TB-1

TB-2

TB-1

TB-2

TB-3

TB-4

TB-5

RELAY CR1

RELAY CR1

HIGH SPEED

CONTROL (EXHAUST BLOWER)

3

5

4

6

Figure F5: CO

2

ventilation control

IMPORTANT

Removal of dry contacts that close on high speed termi-

nals is required for VFDs to modulate.

Advertising