Mammoth 800 to 5500 CFM: Dedicated Outdoor Air System with Enthalpy Wheels (VHC) User Manual
Page 6
MAMM-VHC-IOM-1A (JANUARY 2013)
6
Roofcurbs supplied by others must be designed with the
same dimensions and cross member arrangement as per
Mammoth roofcurb drawings and must be designed to
evenly withstand perimeter and cross section static loads.
Inspect the equipment exterior and interior for damage
and for shipped loose parts. Ensure there is no damage to
internal components such as fans, motors, dampers, en-
thalpy wheel, insulation and structures. File a claim with the
shipping company if the unit is damaged. Check the pack-
ing slip against all items received. If any items are missing,
sign the carrier’s bill of lading with the notation “Shipment
Received Less Item #___.”
Spreader bars are required to prevent damage to the roof
flange. Rollers may be used to move the unit across the
roof. Lifting holes are provided in the base rails as shown in
Appendix C
. Refer to submittal documents for overall unit
dimensions and
Appendix D
for unit weights.
On vertical discharge units, secure all ducts to the roofcurb
and building structure. Do not secure ductwork to the unit.
For unit and duct opening sizes see submittal drawings.
Insulate and weatherproof all external ductwork, joints and
roof openings with counter-flashing and mastic in accor-
dance with applicable codes. Ductwork running through
roof decks must comply with local fire codes. Ducts pass-
ing through unconditioned spaces must be insulated and
covered with a vapor barrier. Flexible connectors should
be installed close to the unit in the duct leading to occupied
spaces to minimize noise transmission.
Duct Design Considerations
The discharge ductwork immediately downstream from the
fan is critical for successful applications. Poorly designed
ductwork can degrade fan performance and contributes to
excessive pressure drop and noise.
When designing ductwork in the field, it is important to
use a straight discharge duct of the correct dimensions to
obtain maximum fan performance. The straight section of
ductwork helps the airflow to develop a uniform velocity
profile as it exits the fan and allows the velocity pressure to
recover into static pressure. See Figure 1
.
For 100% recovery of velocity pressure into static pres-
sure, the straight portion of the discharge duct must be at
least 2.5 times the discharge diameter to the length of the
straight portion of ductwork.
As an example of how to size the straight portion of duct,
assume the fan has a 13.5”x 9.5” discharge outlet = 0.89
ft
2
.
Roofcurbs Supplied by Others
Rigging and Placing the Unit
Field Fabricated Ductwork
IMPORTANT
Mammoth is not liable for any damages, costs or other is-
sues arising from roofcurbs supplied by others.
IMPORTANT
This information is referenced from AMCA Fans and Sys-
tems Publication 201.
IMPORTANT
The hoods for these units are not installed from the fac-
tory and must be installed on site. They should be in-
stalled after the unit is installed. Hoods are shipped on top
of the unit. When rigging the unit, make sure the hoods
are secured and are not damaged by the spreader bars.
See
Appendix B
for hood installation.
CAUTION
All panels must be in place when rigging.
Centrifugal fan
Cutoff
Discharge duct
100% effective duct length
2½ diameters at 2,500 FPM
Figure 1: Duct design