Unoccupied (un) – Mammoth 800 to 5500 CFM: Dedicated Outdoor Air System with Enthalpy Wheels (VHC) User Manual

Page 9

Advertising
background image

MAMM-VHC-IOM-1A (JANUARY 2013)

9

This must come from an optional thermostat or humidistat.

The unit will run in recirc mode upon a call.

Occupied Recirculation (Or) (DDC Control Package

only)

If the occupied recirculation contact closes or a jumper is

placed across terminals, heat wheel starts (not in free cool-

ing), defrost recirculation damper closes (if equipped), out-

side and exhaust air dampers (if equipped) begin to open;

after outside air damper opens fully the supply blower

starts; after exhaust air damper opens fully the exhaust

blower starts, the occupied recirculation damper opens and

outside and exhaust dampers modulate to the minimum

setpoints.

Unoccupied (Un)

If the contact opens or jumper removed on any of the ter-

minals 304, 305, 306, 307 or 308 the unit will turn off.

PNL

FW

PNL

FW

Figure 2: Possible terminal strip locations in electrical panel