Battery management system events, Battery management, System events – APC Battery Management System User Manual
Page 104: User’s guide, Battery management system
®
USER’S GUIDE
Battery Management System
97
Battery Management System events
Code
Severity
Description
0x0801
Informational
System: Communication established.
0x0802
Severe
System: Communication lost.
0x080D
Informational
System: Configuration has been changed.
0x080E
Severe
Charger: String voltage is low.
0x080F
Informational
Charger: Low string voltage returned to normal.
0x0810
Severe
Charger: String voltage is high.
0x0811
Informational
Charger: High string voltage returned to normal.
0x0812
Warning
Charger: High ripple current.
0x0813
Informational
Charger: High ripple current returned to normal.
0x0814
Severe
Charger: String discharging. See
.
0x0815
Informational
Charger: String no longer discharging.
0x0816
Severe
Battery: Cell shorted.
0x0817
Informational
Battery: Cell short cleared.
0x0818
Warning
Management Controller: Open fuse or connection.
0x0819
Informational
Management Controller: Open fuse or connection normal.
0x081A
Severe
Battery: Capacity is low.
0x081B
Informational
Battery: Low capacity is now normal.
0x081C
Warning
Battery: Ohmic value is high.
0x081D
Informational
Battery: High ohmic value is now normal.
0x081E
Severe
Battery: Thermal runaway in progress.
0x081F
Informational
Battery: Thermal runaway no longer in progress.
0x0820
Warning
Battery: Dryout/sulfation present.