Secondary modbus™ port, Figure 30 on-screen keyboard, Unications device, refer to section 5.5 – Detcon 1600A-N1P User Manual

Page 29: See section 5.5 for modbus slave setti, Figure 30), to, 5 secondary modbus™ port

Advertising
background image

1600A-N1P

Figure 30 On-Screen Keyboard

5.5 Secondary Modbus™ Port

Model 1600A controllers feature a Modbus™ compatible communications port and are addressable by a PLC,
PC/HMI, DCS, or other Modbus™ RTU master device. Communication is accomplished by two wire half-
duplex RS-485, 9600 or 19,200 baud, 8 data bits, 1 stop bit, and no parity. Wiring should be brought directly
to the back of the controller (See section 3.0 and

). A Modbus™ RTU master device up to 4,000 feet

away can poll up to 64 different controllers. Noise and/or wiring conditions may limit the number of devices
that can be connected to the Modbus wires. If a multi-point system is being utilized, each controller must be
set to a different device address.

Figure 5


Modbus™ Register Detail:
Read Holding Registers is the only code supported by the 1600A controllers. The 1600A contains 21 holding
registers that reflect the status its 16 channels. The register data is shown below.

Register #
40000

Channel 1 Reading

40001

Channel 2 Reading

40002

Channel 3 Reading

40003

Channel 4 Reading

40004

Channel 5 Reading

40005

Channel 6 Reading

40006

Channel 7 Reading

40007

Channel 8 Reading

40008

Channel 9 Reading

40009

Channel 10 Reading

40010

Channel 11 Reading

40011

Channel 12 Reading

40012

Channel 13 Reading

40013

Channel 14 Reading

40014

Channel 15 Reading

40015

Channel 16 Reading



40016 Fault Status Bits

1600A-N1P Instruction Manual

Rev. 0.1

Page 25 of 40