Figure 35 unbalanced data bus, Figure 36 data bus using two repeaters, Figure 37 repeater wiring diagram – Detcon 1600A-N1P User Manual

Page 38

Advertising
background image

1600A-N1P

Figure 35 Unbalanced Data Bus

The addition of 2 repeaters (Figure 36) can solve this problem. The repeaters look like short stubs to the main
bus, and at the same time they create 2 new buses that have all the same characteristics as the main bus. Each
leg must have termination resistors to balance the new data bus.

Figure 36 Data Bus using two repeaters


Be sure to check the equipment being installed. Some manufacturers include a built-in terminating resistor
that can be selected by a jumper or dipswitch. Detcon Model 880 has such a jumper located on the FA-Isonet
card. The jumper is labeled “120 ohm Term”.

Detcon 600 series gas sensors and DA1 modules do not include this resistor, and therefore, if one of these
devices is the last on the RS-485 bus, a discrete 120 ohm resistor should be placed across the “A” and “B”
terminals on the connector board.

illustrates the wiring scheme of a repeater when used in a wiring

bus with DA-1 devices.

Figure 37

Figure 37 Repeater wiring diagram

1600A-N1P Instruction Manual