Gas Control Installations
For gas control installations, there are choices for VFM 3100 location
that should be considered. For maximum rangeability, locate the
VFM 3100 30 or more pipe diameters downstream from a control
valve. This will assure maximum velocity at the VFM 3100 and pro-
duce the most efficient signal from the sensor.
When the flow is more stable, the VFM 3100 may be mounted a mini-
mum of 5 pipe diameters upstream of the control valve. Pressure
fluctuations often are less on the upstream side of a control valve.
This should be considered as a means to provide the most accurate
density when a flow computer is not used.
The VFM 3100 electronics automatically calculates the effect of up-
stream piping on K-factor when installation piping data is entered by
user.
Steam Control Installations
For steam control installations, it is recommended that the VFM 3100
be mounted 30 pipe diameters or more downstream of the control
valve. This is particularly useful when measuring saturated steam to
ensure that there is a minimum amount of condensate present at the
VFM 3100.
Pressure and Temperature Taps
NOTE: The inside of the pipe at the pressure and temperature taps
must be free of burrs and obstructions.
Pressure Taps -- For density measurement (when required),
locate the tap 3-1/2 to 4-1/2 pipe diameters DOWNSTREAM
of the VFM 3100. See Figure 5.
NOTE: On a gas installation, the pressure tap should be located on
the top of the pipe. On a liquid installation, the pressure tap (if requi-
red) should be located on the side of the pipe. On a steam installa-
tion, the pressure tap should be located on the top when the pressure
measuring device (typically a pressure transmitter) is above the
pipeline, and on the side when the measuring device is below the
pipeline. With vertical piping, the pressure tap may be located any-
where around the circumference of the pipeline.
Temperature Taps -- For temperature measurement (when re-
quired), locate the tap 5 to 6 pipe diameters DOWNSTREAM of
the VFM 3100. The smallest possible probe is recommended to
reduce flow disturbance. See Figure 5.
10
1.2.2. Installation Position
For optimal performance the locations of the sensor and integral
electronics relative to the piping must be considered. Factors that
influence this decision include process fluid type, ambient tempera-
ture, and vibration.
Process Fluid
When using:
Saturated Steam: The electronics housing should be below the
VFM 3100 body, so that the sensor cavity remains filled with conden-
sate.
NOTE: A VFM3100 used on steam should be located downstream
of a control valve.See "Steam Control Installations."
Superheated Steam: The electronics housing should be below the
VFM 3100 body when the steam has less than 10 °F (5.6 °C) super-
heat. The housing should be above the VFM 3100 body when the
superheat is more than 10 °F and no condensate will be forming on
the sensor. An isolation valve may be used in superheated steam
applications with adequate insulation.
Gas: The electronics housing may be above or below the VFM 3100
body. The normal recommended position of the electronics housing
is above the VFM 3100 body.
Liquid: For a liquid with solid particles, the electronics housing
should be above the VFM 3100 body. Care should be taken so that
entrapped air does not accumulate in the sensor cavity. For a clean
liquid, the electronics housing may be mounted below the VFM 3100
body. Care must be taken if there is any sediment or fine dirt, that the
particles do not accumulate in the sensor cavity. A VFM 3100 used
on liquid should be mounted upstream from a control valve.
VFM 3100 may also be mounted with the electronics housing posi-
tioned to the side. This ensures escape of entrapped air and mini-
mizes sediment accumulation.
The above considerations are summarized in Table 3 for single and
dual measurement VFM 3100 with and without isolation valves.
1.2.3. Ambient Temperature
Ambient temperature limits must be observed per specifications.
However, if the electronic housing is above the ambient temperature
limit (85 °C, 185 °F), the VFM 3100 may be mounted with the electro-
nic housing located to the side to aid the cooling of the electronic
module. The bottom conduit connection shoud be used (the top one
plugged) to avoid possible accumulation of condensate at the termi-
nal block.
1.2.4. Vibration
The vortex shedder axis should be oriented to reduce or, in some ca-
ses virtually eliminate, vibration influence. Positioning VFM3100 so
that vibrations are parallel to sensor diaphragms will minimize effect
of vibrations.
Pressure Tap
Temperature Tap
Direction of Flow
Figure 5. Pressure and Temperature Tap Locations
- BATCHFLUX 5500 C Quickstart EN
- IFC 050 Converter Quickstart EN
- IFC 100 Converter Quickstart EN
- IFC 300 Converter Quickstart EN
- OPTIFLUX 1000 Quickstart EN
- OPTIFLUX 2000 Quickstart EN
- OPTIFLUX 4000 Quickstart EN
- OPTIFLUX 4040C Quickstart EN
- OPTIFLUX 5000 Flange Quickstart EN
- OPTIFLUX 5000 Sandwich Quickstart EN
- OPTIFLUX 6000 Quickstart EN
- OPTIFLUX 7300 Quickstart EN
- OPTIPROBE Quickstart EN
- TIDALFLUX 2300 F EN
- TIDALFLUX 2300 F Quickstart EN
- WATERFLUX 3000 EN
- WATERFLUX 3000 Quickstart EN
- WATERFLUX 3070 EN
- WATERFLUX 3070 Quickstart EN
- USB ADAPTER PLUS EMF EN
- IFC 050 Converter Modbus EN
- IFC 100 Converter FOUNDATION FIELDBUS EN
- IFC 100 Converter Modbus EN
- IFC 300 Converter FOUNDATION FIELDBUS EN
- IFC 300 Converter HART 0102 EN
- IFC 300 Converter HART 0201 EN
- IFC 300 Converter Modbus EN
- IFC 300 Converter PROFIBUS PA DP EN
- OPTIFLUX 2000-4000 IECEx EN
- OPTIFLUX 2000-4000-5000-6000-7300-IFC 300 Ex EN
- OPTIFLUX 2000-4000-5000-6000 -IFC 100 Ex EN
- OPTIFLUX 4040 C Ex EN
- OPTIFLUX x300 Ex Zone2 EN
- H250 M9 ES EN
- VA 40-VA 45 EN
- H250 M10 ATEX II2G Ex d EN
- H250 M10 ATEX II3D Ex t EN
- H250 M40 ATEX II2D Ex t-II2G Ex d EN
- H250 M40 ATEX II2G Ex i EN
- H250 M40 ATEX II3G Ex nA EN
- H250 M40 Ex II2G Reed EN
- H250 M9 ATEX II2G Ex i EN
- H250 M9S ATEX II3D Ex t-II3G Ex nA EN
- M8E Converter HART 0101 EN
- DK 32-DK 34 ATEX II2G Ex i EN
- DK 32-DK 34 ATEX II3G Ex nA-ic EN
- DK 37-H250 M8 ATEX II2G Ex i EN
- DK 46-47-48-800 ATEX II2G Ex i EN
- ESK4 Ex II2G Ex iEN
- ESKII ESK3 PA ATEX II2G Ex i EN
- GA 24 ATEX II2G Ex i EN
- H250 M40 Safety V1 EN
- H250 M9 Safet V1 EN
- DK 32-DK 34-DK 37 Safety V1 EN
- H250 M40 Safety V2 EN
- H250 M9 Safet V2 EN
- DK 32-DK 34-DK 37 Safety V2 EN
- OPTISONIC 3400 EN
- OPTISONIC 3400 Quickstart EN
- OPTISONIC 6300 EN
- OPTISONIC 6300 P-6400 EN
- OPTISONIC 6300 Quickstart EN
- OPTISONIC 7300 EN
- OPTISONIC 7300 Quickstart EN
- UFM 3030 Service EN
- UFM 3030 EN
- UFM 530 HT EN
- UFM 610P EN
- UFM 800 EN
- ALTOSONIC V EEx EN
- ALTOSONIC V Installation EN
- OPTISONIC 3400 CSA EN
- OPTISONIC 3400 Ex EN
- OPTISONIC 6300 EEx EN
- OPTISONIC 7300 Ex EN
- OPTIMASS 8000K EN
- MFC 300 FOUNDATION FIELDBUS EN
- OPTIMASS Sensors Concentration Measurement EN
- OPTISWIRL 4070 EN
- OPTISWIRL 4070 Quickstart EN
- VFM 5090 EN
- OPTISWIRL 4070 ATEX II2G EN
- DA Flap-type EN
- DW 181-182-183-184 ATEX EN
- OPTIFLEX 1100C Quickstart EN
- OPTIFLEX 2200 C_F Quickstart EN
- OPTIWAVE 5200 C_F EN
- OPTIWAVE 5200 C_F Quickstart EN
- OPTIWAVE 6300C EN
- OPTIWAVE 6300C Quickstart EN
- OPTIWAVE 7300C EN
- OPTIWAVE 7300C Quickstart EN
- OPTISOUND 3000 Series EN
- OPTISOUND 3010C 2wire EN
- OPTISOUND 3010C 4wire EN
- OPTISOUND 3020C 2wire EN
- OPTISOUND 3020C 4wire EN
- OPTISOUND 3030C 2wire EN
- OPTISOUND 3030C 4wire EN
- BM 26 BASIC_ADVANCED Quickstart EN
- BM 26 BASIC-ADVANCED ATEX EN
- OPTIFLEX 1300 C WHG EN
- OPTIFLEX 2200 ATEX EN
- OPTISOUND 3010-3020 Ex DE
- OPTIWAVE 5200 ATEX EN
- OPTIFLEX 1300C ATEX EN
- OPTIFLEX 4300C ATEX EN
- BM 70A EEx EN
- BM 70A-P PROFIBUS PA EN
- BW 25 Ex II 1-2 G EN
- OPTISWITCH 6500 C EN
- OPTISWITCH 6600 C EN
- OPTISWITCH 3000C 2wire EN
- OPTISWITCH 3000C Contactless EN
- OPTISWITCH 3000C NAMUR EN
- OPTISWITCH 3000C Relay EN
- OPTISWITCH 3000C Transistor EN
- OPTISWITCH 3100C 2wire EN
- OPTISWITCH 3100C Contactless EN
- OPTISWITCH 3100C NAMUR EN
- OPTISWITCH 3100C Relay EN
- OPTISWITCH 3100C Transistor EN
- OPTISWITCH 3200C 2wire EN
- OPTISWITCH 3200C Contactless EN
- OPTISWITCH 3200C NAMUR EN
- OPTISWITCH 3200C Relay EN
- OPTISWITCH 3200C Transistor EN
- OPTISWITCH 3300C 2wire EN
- OPTISWITCH 3300C ARV33 16bar EN
- OPTISWITCH 3300C ARV33 unpressurized EN
- OPTISWITCH 3300C Contactless EN
- OPTISWITCH 3300C NAMUR EN
- OPTISWITCH 3300C Relay EN
- OPTISWITCH 3300C Transistor EN
- OPTISWITCH 4000C Contactless EN
- OPTISWITCH 4000C Transistor EN
- OPTISWITCH 5100C 2wire EN
- OPTISWITCH 5100C Contactless EN
- OPTISWITCH 5100C Namur EN
- OPTISWITCH 5100C Relay EN
- OPTISWITCH 5100C Transistor EN
- OPTISWITCH 5200C 2wire EN
- OPTISWITCH 5200C Contactless EN
- OPTISWITCH 5200C Namur EN
- OPTISWITCH 5200C Relay EN
- OPTISWITCH 5200C Transistor EN
- OPTISWITCH 52x0C ARV52 16bar EN
- OPTISWITCH 52x0C ARV52 64bar EN
- OPTISWITCH 52x0C ARV52 unpressurized EN
- OPTISWITCH 3x00 EX II1_2D-II2D-IP66T DE
- OPTISWITCH 3x00 Ex II1_2G-II2G-EExd IICT6 DE
- OPTISWITCH 3x00C 2wire SIL EN
- OPTISWITCH 3x00C Contactless SIL EN
- OPTISWITCH 3x00C NAMUR SIL EN
- OPTISWITCH 3x00C Relay SIL EN
- OPTISWITCH 3x00C Transistor SIL EN
- OPTISWITCH 5xx0C 2wire SIL EN
- OPTISWITCH 5xx0C Contactless SIL EN
- OPTISWITCH 5xx0C NAMUR SIL EN
- OPTISWITCH 5xx0C Relay SIL EN
- OPTISWITCH 5xx0C Transistor SIL EN
- OPTITEMP TR 100-TC 100 EN
- OPTITEMP TRA-TCA EN
- OPTITEMP TRA-TCA Plus EN
- TTP 200 EN
- OPTITEMP TT 10 C-R EN
- OPTITEMP TT 11 C-R EN
- PTITEMP TT 20 C EN
- OPTITEMP TT 30 C-R EN
- OPTITEMP TT 31 R EN
- OPTITEMP TT 50 C-R EN
- OPTITEMP TT 51 EN
- OPTITEMP TT 60 C-R EN
- OPTITEMP ConSoft TT 20-51 EN
- OPTITEMP ConSoft TT 20-51 ES
- OPTITEMP LCD-H20 EN
- OPTITEMP TR 100 Ex EN
- OPTITEMP TRA Ex EN
- PTD 500 EN
- PTD 600 EN
- OPTIBAR P 1010 C Ex EN
- OPTIBAR PC 5060 C Ex d ia EN
- OPTIBAR PC 5060 C Ex ia EN
- MAC 100 EN
- OPTISENS ORP 8590 EN
- OPTISENS PH 8100 EN
- OPTISENS PH 8300 EN
- OPTISENS PH 8390 EN
- OPTISENS PH 8500 EN
- OPTISENS PH 9100 EN
- SMARTSENS ORP 1590 EN
- SMARTSENS ORP 8150 EN
- SMARTSENS ORP 8510 EN
- SMARTSENS PH 1590 EN
- SMARTSENS PH 2390 EN
- SMARTSENS PH 8150 EN
- SMARTSENS PH 8320 EN
- SMARTSENS PH 8510 EN
- SMARTSENS PH 8530 EN
- SMARTSENS PH 8570 EN
- OPTISYS TUR 1050 EN
- OPTISENS COND 1200 EN
- OPTISENS CL 1100 EN
- OPTISYS CL 1100 EN
- OPTISYS SLM 2100 EN
- PipePatro EN
- SU 501 EX EN
- SU 600 EN
- SU 600 Ex EN
- H250 M9 PROFIBUS PA EN
- IFC 070 Converter EN
- IFC 070 Converter EN
- CAPAFLUX IFM 5080 K Datasheet EN
- IFC 010 Converter Short EN
- IFC 020 Short EN
- IFC 070 Converter Quickstart EN
- IFC 210 E Short EN
- OPTIFLUX 2070 Quickstart EN
- OPTIFLUX 7000 Quickstart EN
- PROFIFLUX IFS 5000 EN
- TIDALFLUX IFM 4110 PF EN
- TIDALFLUX 4300 F EN
- TIDALFLUX 4300 F Quickstart EN
- VARIFLUX 6000 EN
- VARIFLUX IFS 6000 EN
- MAGCHECK EN
- MAGCHECK EN
- ALTOFLUX 2W IFM 4042K EEx-ATEX EN
- ALTOFLUX IFS 4000 F-EEx EN
- ALTOFLUX IFM 4080 K-EEx-i-EEx EN
- ALTOFLUX IFM 4080 K EEx EN
- ALTOFLUX IFM 5080 K EEx EN
- ALTOFLUX IFM 6080 K EEx EN
- ALTOFLUX IFM x080 K ATEX EN
- ALTOFLUX IFM4042K EEx EN
- CAPAFLUX EEx-ATEX EN
- IFC 090 Converter PROFIBUS PA EN
- IFC 090F Converter EEx-ATEX EN
- M10 Converter H250-H 54 Ex II2G EN
- UFM 500 EN
- UFM 600T EN
- CORIMASS E P MFM 3081 EEx EN
- CORIMASS MFC 81 EN
- CORIMASS MFC 81 Interface EN
- CORIMASS MFC 81 Modis EN
- OPTISOUND 3040 C 4wire EN
- OPTISOUND 3050C 4wire EN
- BM 100A ATEX EN
- BM 100A PROFIBUS PA EN
- BM 102 ATEX EN
- OPTISOUND 3040 Ex EN
- OPTISENS AAC 050 EN
- OPTISENS AAM 2080 EN
- OPTISENS AAS 2000 EN
- OPTISENS CAC 050 EN
- OPTISENS MAC 080 EN
- OPTISENS OAM 2080 EN
- OPTISENS OAS 2000 EN
- OPTISENS PAC 050 EN
- OPTISENS PAS 2000 EN
- H250 M40 NEPSI Ex d-Ex t
- H250 M40 NEPSI Ex ia
- H250 M40 NEPSI Ex nA
- DK 32-DK 34 NEPSI Ex i
- H250 M9 NEPSI Ex nA
- DK 32-DK 34 NEPSI Ex nA
- DK 37 NEPSI Ex i
- H250 M40 FOUNDATION FIELDBUS
- H250 M40 PROFIBUS PA
- ESKII HART
- GFC 300 FOUNDATION FIELDBUS
- GFC 300 Modbus
- UFC 030 PROFIBUS PA
- MFC 300 Modbus
- MFC 300 Profibus
- MFC 400 FOUNDATION FIELDBUS
- MFC 400 Modbus
- MFC 400 Profibus
- VFM 1091
- Summit 8800 Vol 1
- Summit 8800 Vol 2
- Summit 8800 Vol 3
- OPTIFLEX 1300C FOUNDATION FIELDBUS
- OPTIFLEX 1300C PROFIBUS PA
- OPTIFLEX 2200 cFMus
- PTIFLEX 2200 FOUNDATION FIELDBUS
- OPTIFLEX 2200 IECEX
- OPTIFLEX 2200 PROFIBUS
- OPTIWAVE 5200 PROFIBUS
- OPTIFLEX 2200C SIL
- OPTIFLEX Hart
- OPTIWAVE Hart
- OPTIFLEX 1300 IECEx
- BM 70 A-P
- OPTITEMP Compact sensors
- OPTISENS PH 8590
- OPTISENS PH 9500
- IFC 090 Converter FOUNDATION FIELDBUS
- ALTOFLUX 2W IFM 4042K
- IFC 010 Converter HART
- IFC 090 Converter HART
- IFC 090 Converter PROFIBUS
- OPTISONIC V6 Modbus
- BM 100 HART
- BM 102 HART
- BATCHCONTROL 5014 C
- BATCHFLUX 5500 C EN
- IFC 050 Converter EN
- IFC 100 Converter EN
- IFC 300 Converter EN
- IFC 300 Converter ES
- OPTIFLUX 1000 EN
- OPTIFLUX 2000 EN
- OPTIFLUX 4000 EN
- OPTIFLUX 5000 Flange EN
- OPTIFLUX 5000 Sandwich EN
- OPTIFLUX 6000 EN
- OPTIFLUX 7300 EN
- TIDALFLUX 2300 F Ex EN
- H250 M40 EN
- H250 M8-M9-M10 EN
- DK 32 Purge EN
- DK 32-DK 34-DK 37 EN
- DK 46-47-48-800 EN
- DK 46 I-DK 47 I EN
- DK 700 EN
- GA 24 EN
- H250 Reed MS14 EN
- VA 40 ATEX II2G Ex i EN
- VA FLOWMETERS EN
- ALTOSONIC III EN
- ALTOSONIC V EN
- ALTOSONIC V12 EN
- ALTOSONIC V Modbus EN
- UFC 400 FOUNDATION FIELDBUS EN
- UFC 400 Modbus EN
- UFM 3030 EEx EN
- UFM 800 Hot-Tap EN
- MFC 300 EN
- MFC 400 EN
- OPTIBATCH 4011 C EN
- OPTIGAS 4010 C EN
- OPTIMASS 1000 EN
- OPTIMASS 2000 EN
- OPTIMASS 3000 EN
- OPTIMASS 6000 EN
- OPTIMASS 7000 EN
- OPTIMASS with MFC 300 EN
- OPTIMASS Sensors Corrosion guidelines EN
- DW 181-182-183-184 EN
- DWM 1000-2000 EN
- OPTIFLEX 1100C EN
- OPTIFLEX 1300C EN
- OPTIFLEX 2200 C_F EN
- BM 26 A EN
- BM 26 BASIC_ADVANCED EN
- BM 500 EN
- BM 70 A_P EN
- BM 700 EN
- BM 702 EN
- BM 702 A EN
- BW 25 EN
- OPTIWAVE 7300 WHG Overfill Protection EN
- OPTIWAVE 6300C ATEX EN
- OPTIWAVE 7300C ATEX EN
- OPTIWAVE 8300C Marine ATEX EN
- LEM 300 EN
- LS 72xx EN
- TT 51 SERIES EN
- OPTIBAR DP 7060 C EN
- OPTIBAR P 1010 C EN
- OPTIBAR P 2010 C EN
- OPTIBAR P 3050 C EN
- OPTIBAR PC 5060 C EN
- ACM 500 EN
- SMARTSENS ORP 8150 Ex EN
- SMARTSENS PH 8xxx Ex EN
- C95 CI EN
- ALTOFLUX 2W IFM 4042K EN
- ALTOFLUX IFS 4000 EN
- ALTOFLUX M 900 EN
- AQUAFLUX EN
- BATCHFLUX 5015 K EN
- ECOFLUX IFS 1000 EN
- IFC 010 Converter EN
- IFC 020 Converter EN
- IFC 090 Converter EN
- IFC 110 Converter EN
- IFC 210 E EN
- OPTIFLUX 2070 EN
- H54 M4 EN
- GFM 700 EN
- OPTISONIC 7060 EN
- UFM 500 ATEX EN
- CORIMASS P Series EN
- CORIMASS G-MFM 4085 EN
- OPTIMASS with MFC 05x EN
- CORIMASS G-MFM 4085 EEx EN
- BM 100A EN
- BM 102 EN
- BM 90 EN
- LS 4100 EN
- LS 6500 EN
- LS 6600 EN
- M10 Converter HART 0201
- UFC 030 HART
- UFC 400 PROFIBUS PA-PROFIBUS DP
- MFC 010 C Converter
- OPTIMASS 2400
- DWM 2000 LCD
- BM 70 M
- CARGOMASTER
- OPTIWAVE 5200 cFMus
- OPTIWAVE 5200 FOUNDATION FIELDBUS
- OPTIWAVE 5200 IECEx
- OPTIWAVE 5200C SIL
- OPTIWAVE 6300 IECEx
- OPTIWAVE 6300C FOUNDATION FIELDBUS
- OPTIWAVE 6300C PROFIBUS PA
- OPTIWAVE 7300C FOUNDATION FIELDBUS
- OPTIWAVE 7300C PROFIBUS PA
- OPTIWAVE 7300 IECEx
- IFC 110 Converter
- IFC 110 Converter HART V0201
- UFC 500 HART
- BM 100A Handbook
- BM 102 Handbook