Determining special measuring units, Isolation valves, Replacing the sensor – KROHNE VFM 3100 EN User Manual
Page 43
43
5. Determining Special Measuring Units
There may be a need to use flow units that are not listed in the units
menu. To enter custom units, select “special” from the flow and/or
total units menu.
The following four entries are required to configure the transmitter for
special flow and total units.
•
Total name, maximum six characters,
is required for displaying total.
•
Flow name, maximum six characters,
is required for displaying the flow rate.
•
Total conversion factor for computing total.
•
Flow conversion factor for computing flow.
The conversion factors must be related to the internal software and
the manner in which the VFM 3100 computes flow. The conversion
factor for total is a direct conversion from ft
3
to the desired units. The
conversion factor for flow is a direct conversion from ft
3
/sec to the
desired flow units. Any table of conversion factors may be used.
Example: Barrels per hour
To measure total in barrels and flow in barrels per hour.
Total Name:
bbl
Flow Name:
bbl/h
Total Conversion Factor: 0.1781 bbl/ft
3
Flow Conversion Factor: 0.1781 x 3600 = 641.2 bbl/h
where:
3600 = sec/hr
Example:
BTU per minute
The conversion factor for total must be in BTU/ft
3
. If the BTU factor is
known in mass units, then it must be converted to volume units by
multiplying by density. The flow factor is a direct conversion from
ft
3
/sec to the desired units.
Total Name:
BTU
Flow Name:
BTU/m
Total Conversion Factor: (BTU/lb) x density
Flow Conversion Factor: (BTU/lb) x density x 60
where:
60 = sec/min
Example:
Calories per hour
The conversion factor for total must be in calories/ft
3
. If the calories
factor is known in cal/kg, it must be converted to cal/ft
3
by multiplying
by the density and volume conversion factors (m
3
to ft
3
). The flow fac-
tor must be related to ft
3
/sec.
Total Name:
cal
Flow Name:
cal/h
Total Conversion Factor: (cal/kg) x density x 0.028317
where:
0.028317 = m
3
/ft
3
Flow Conversion Factor: (cal/kg) x density x 0.028317 x 3600
6. Isolation Valves
Isolation valving is available in single and dual measurement versions
for standard and extended range sensors. The following procedure
applies to all versions. Replacing the sensor in this type of unit is
essentially the same as replacing a sensor in units without isolation
valving. However, particular care must be taken since the process
does not need to be shut down.
WARNING: The isolation valve must be in the closed position prior
to replacing the sensor. It must be gradually depressurized so that
process fluid does not leak. Personal injury could result from such a
leak. Follow normal lockout procedures. Remove power from the
VFM 3100.
6.1. Replacing the Sensor
•
Close the valve. This is a dual port, single ball 1/4-turn valve.
Use a wrench on the flat on the valve stem to turn clockwise
one quarter turn. See Figure 38.
NOTE: The right angle position indicator attached to the stem is not
a valve handle. Use a wrench on the valve stem flats.
•
Allow the unit to cool down as required.
•
Remove power from the VFM 3100 and disconnect input wiring
and conduit connections.
•
Gradually loosen the four top bolts that connect the mechanical
connector to top surface of the valve body. Do not loosen the
bottom bolts.
•
Allow trapped process fluid within valve body to depressurize.
•
Remove the four connector bolts and lift off electrical housing,
mechanical connector, and Sensor as a unit.
NOTE: If electronic housing cover cannot be removed by hand, it
may be necessary to insert a flat bar in slot to remove.
•
Proceed to remove the electronic module per instructions
starting on page 30 and replace the sensor per instructions
starting on page 38. Be sure the O-ring is installed on the
sensor and use a new flow dam and gasket.
•
When the new sensor has been installed, mount the sensor and
mechanical connector to the valve body and tighten the bolts
per instructions starting on page 38.
•
Since it is not possible to leak test the valve-to-connector joint,
it must be assembled carefully.
•
Open the valve counterclockwise. Use care and check for leaks.
•
Reinstall the electronic module and, when required, the pream-
plifier, using instructions starting on page 35.
•
Reconnect the conduit and external wiring.
Refer to instructions starting on page 13.
•
Replace the covers and resume operation. There should be no
need to recalibrate the electronic module.
- BATCHFLUX 5500 C Quickstart EN
- IFC 050 Converter Quickstart EN
- IFC 100 Converter Quickstart EN
- IFC 300 Converter Quickstart EN
- OPTIFLUX 1000 Quickstart EN
- OPTIFLUX 2000 Quickstart EN
- OPTIFLUX 4000 Quickstart EN
- OPTIFLUX 4040C Quickstart EN
- OPTIFLUX 5000 Flange Quickstart EN
- OPTIFLUX 5000 Sandwich Quickstart EN
- OPTIFLUX 6000 Quickstart EN
- OPTIFLUX 7300 Quickstart EN
- OPTIPROBE Quickstart EN
- TIDALFLUX 2300 F EN
- TIDALFLUX 2300 F Quickstart EN
- WATERFLUX 3000 EN
- WATERFLUX 3000 Quickstart EN
- WATERFLUX 3070 EN
- WATERFLUX 3070 Quickstart EN
- USB ADAPTER PLUS EMF EN
- IFC 050 Converter Modbus EN
- IFC 100 Converter FOUNDATION FIELDBUS EN
- IFC 100 Converter Modbus EN
- IFC 300 Converter FOUNDATION FIELDBUS EN
- IFC 300 Converter HART 0102 EN
- IFC 300 Converter HART 0201 EN
- IFC 300 Converter Modbus EN
- IFC 300 Converter PROFIBUS PA DP EN
- OPTIFLUX 2000-4000 IECEx EN
- OPTIFLUX 2000-4000-5000-6000-7300-IFC 300 Ex EN
- OPTIFLUX 2000-4000-5000-6000 -IFC 100 Ex EN
- OPTIFLUX 4040 C Ex EN
- OPTIFLUX x300 Ex Zone2 EN
- H250 M9 ES EN
- VA 40-VA 45 EN
- H250 M10 ATEX II2G Ex d EN
- H250 M10 ATEX II3D Ex t EN
- H250 M40 ATEX II2D Ex t-II2G Ex d EN
- H250 M40 ATEX II2G Ex i EN
- H250 M40 ATEX II3G Ex nA EN
- H250 M40 Ex II2G Reed EN
- H250 M9 ATEX II2G Ex i EN
- H250 M9S ATEX II3D Ex t-II3G Ex nA EN
- M8E Converter HART 0101 EN
- DK 32-DK 34 ATEX II2G Ex i EN
- DK 32-DK 34 ATEX II3G Ex nA-ic EN
- DK 37-H250 M8 ATEX II2G Ex i EN
- DK 46-47-48-800 ATEX II2G Ex i EN
- ESK4 Ex II2G Ex iEN
- ESKII ESK3 PA ATEX II2G Ex i EN
- GA 24 ATEX II2G Ex i EN
- H250 M40 Safety V1 EN
- H250 M9 Safet V1 EN
- DK 32-DK 34-DK 37 Safety V1 EN
- H250 M40 Safety V2 EN
- H250 M9 Safet V2 EN
- DK 32-DK 34-DK 37 Safety V2 EN
- OPTISONIC 3400 EN
- OPTISONIC 3400 Quickstart EN
- OPTISONIC 6300 EN
- OPTISONIC 6300 P-6400 EN
- OPTISONIC 6300 Quickstart EN
- OPTISONIC 7300 EN
- OPTISONIC 7300 Quickstart EN
- UFM 3030 Service EN
- UFM 3030 EN
- UFM 530 HT EN
- UFM 610P EN
- UFM 800 EN
- ALTOSONIC V EEx EN
- ALTOSONIC V Installation EN
- OPTISONIC 3400 CSA EN
- OPTISONIC 3400 Ex EN
- OPTISONIC 6300 EEx EN
- OPTISONIC 7300 Ex EN
- OPTIMASS 8000K EN
- MFC 300 FOUNDATION FIELDBUS EN
- OPTIMASS Sensors Concentration Measurement EN
- OPTISWIRL 4070 EN
- OPTISWIRL 4070 Quickstart EN
- VFM 5090 EN
- OPTISWIRL 4070 ATEX II2G EN
- DA Flap-type EN
- DW 181-182-183-184 ATEX EN
- OPTIFLEX 1100C Quickstart EN
- OPTIFLEX 2200 C_F Quickstart EN
- OPTIWAVE 5200 C_F EN
- OPTIWAVE 5200 C_F Quickstart EN
- OPTIWAVE 6300C EN
- OPTIWAVE 6300C Quickstart EN
- OPTIWAVE 7300C EN
- OPTIWAVE 7300C Quickstart EN
- OPTISOUND 3000 Series EN
- OPTISOUND 3010C 2wire EN
- OPTISOUND 3010C 4wire EN
- OPTISOUND 3020C 2wire EN
- OPTISOUND 3020C 4wire EN
- OPTISOUND 3030C 2wire EN
- OPTISOUND 3030C 4wire EN
- BM 26 BASIC_ADVANCED Quickstart EN
- BM 26 BASIC-ADVANCED ATEX EN
- OPTIFLEX 1300 C WHG EN
- OPTIFLEX 2200 ATEX EN
- OPTISOUND 3010-3020 Ex DE
- OPTIWAVE 5200 ATEX EN
- OPTIFLEX 1300C ATEX EN
- OPTIFLEX 4300C ATEX EN
- BM 70A EEx EN
- BM 70A-P PROFIBUS PA EN
- BW 25 Ex II 1-2 G EN
- OPTISWITCH 6500 C EN
- OPTISWITCH 6600 C EN
- OPTISWITCH 3000C 2wire EN
- OPTISWITCH 3000C Contactless EN
- OPTISWITCH 3000C NAMUR EN
- OPTISWITCH 3000C Relay EN
- OPTISWITCH 3000C Transistor EN
- OPTISWITCH 3100C 2wire EN
- OPTISWITCH 3100C Contactless EN
- OPTISWITCH 3100C NAMUR EN
- OPTISWITCH 3100C Relay EN
- OPTISWITCH 3100C Transistor EN
- OPTISWITCH 3200C 2wire EN
- OPTISWITCH 3200C Contactless EN
- OPTISWITCH 3200C NAMUR EN
- OPTISWITCH 3200C Relay EN
- OPTISWITCH 3200C Transistor EN
- OPTISWITCH 3300C 2wire EN
- OPTISWITCH 3300C ARV33 16bar EN
- OPTISWITCH 3300C ARV33 unpressurized EN
- OPTISWITCH 3300C Contactless EN
- OPTISWITCH 3300C NAMUR EN
- OPTISWITCH 3300C Relay EN
- OPTISWITCH 3300C Transistor EN
- OPTISWITCH 4000C Contactless EN
- OPTISWITCH 4000C Transistor EN
- OPTISWITCH 5100C 2wire EN
- OPTISWITCH 5100C Contactless EN
- OPTISWITCH 5100C Namur EN
- OPTISWITCH 5100C Relay EN
- OPTISWITCH 5100C Transistor EN
- OPTISWITCH 5200C 2wire EN
- OPTISWITCH 5200C Contactless EN
- OPTISWITCH 5200C Namur EN
- OPTISWITCH 5200C Relay EN
- OPTISWITCH 5200C Transistor EN
- OPTISWITCH 52x0C ARV52 16bar EN
- OPTISWITCH 52x0C ARV52 64bar EN
- OPTISWITCH 52x0C ARV52 unpressurized EN
- OPTISWITCH 3x00 EX II1_2D-II2D-IP66T DE
- OPTISWITCH 3x00 Ex II1_2G-II2G-EExd IICT6 DE
- OPTISWITCH 3x00C 2wire SIL EN
- OPTISWITCH 3x00C Contactless SIL EN
- OPTISWITCH 3x00C NAMUR SIL EN
- OPTISWITCH 3x00C Relay SIL EN
- OPTISWITCH 3x00C Transistor SIL EN
- OPTISWITCH 5xx0C 2wire SIL EN
- OPTISWITCH 5xx0C Contactless SIL EN
- OPTISWITCH 5xx0C NAMUR SIL EN
- OPTISWITCH 5xx0C Relay SIL EN
- OPTISWITCH 5xx0C Transistor SIL EN
- OPTITEMP TR 100-TC 100 EN
- OPTITEMP TRA-TCA EN
- OPTITEMP TRA-TCA Plus EN
- TTP 200 EN
- OPTITEMP TT 10 C-R EN
- OPTITEMP TT 11 C-R EN
- PTITEMP TT 20 C EN
- OPTITEMP TT 30 C-R EN
- OPTITEMP TT 31 R EN
- OPTITEMP TT 50 C-R EN
- OPTITEMP TT 51 EN
- OPTITEMP TT 60 C-R EN
- OPTITEMP ConSoft TT 20-51 EN
- OPTITEMP ConSoft TT 20-51 ES
- OPTITEMP LCD-H20 EN
- OPTITEMP TR 100 Ex EN
- OPTITEMP TRA Ex EN
- PTD 500 EN
- PTD 600 EN
- OPTIBAR P 1010 C Ex EN
- OPTIBAR PC 5060 C Ex d ia EN
- OPTIBAR PC 5060 C Ex ia EN
- MAC 100 EN
- OPTISENS ORP 8590 EN
- OPTISENS PH 8100 EN
- OPTISENS PH 8300 EN
- OPTISENS PH 8390 EN
- OPTISENS PH 8500 EN
- OPTISENS PH 9100 EN
- SMARTSENS ORP 1590 EN
- SMARTSENS ORP 8150 EN
- SMARTSENS ORP 8510 EN
- SMARTSENS PH 1590 EN
- SMARTSENS PH 2390 EN
- SMARTSENS PH 8150 EN
- SMARTSENS PH 8320 EN
- SMARTSENS PH 8510 EN
- SMARTSENS PH 8530 EN
- SMARTSENS PH 8570 EN
- OPTISYS TUR 1050 EN
- OPTISENS COND 1200 EN
- OPTISENS CL 1100 EN
- OPTISYS CL 1100 EN
- OPTISYS SLM 2100 EN
- PipePatro EN
- SU 501 EX EN
- SU 600 EN
- SU 600 Ex EN
- H250 M9 PROFIBUS PA EN
- IFC 070 Converter EN
- IFC 070 Converter EN
- CAPAFLUX IFM 5080 K Datasheet EN
- IFC 010 Converter Short EN
- IFC 020 Short EN
- IFC 070 Converter Quickstart EN
- IFC 210 E Short EN
- OPTIFLUX 2070 Quickstart EN
- OPTIFLUX 7000 Quickstart EN
- PROFIFLUX IFS 5000 EN
- TIDALFLUX IFM 4110 PF EN
- TIDALFLUX 4300 F EN
- TIDALFLUX 4300 F Quickstart EN
- VARIFLUX 6000 EN
- VARIFLUX IFS 6000 EN
- MAGCHECK EN
- MAGCHECK EN
- ALTOFLUX 2W IFM 4042K EEx-ATEX EN
- ALTOFLUX IFS 4000 F-EEx EN
- ALTOFLUX IFM 4080 K-EEx-i-EEx EN
- ALTOFLUX IFM 4080 K EEx EN
- ALTOFLUX IFM 5080 K EEx EN
- ALTOFLUX IFM 6080 K EEx EN
- ALTOFLUX IFM x080 K ATEX EN
- ALTOFLUX IFM4042K EEx EN
- CAPAFLUX EEx-ATEX EN
- IFC 090 Converter PROFIBUS PA EN
- IFC 090F Converter EEx-ATEX EN
- M10 Converter H250-H 54 Ex II2G EN
- UFM 500 EN
- UFM 600T EN
- CORIMASS E P MFM 3081 EEx EN
- CORIMASS MFC 81 EN
- CORIMASS MFC 81 Interface EN
- CORIMASS MFC 81 Modis EN
- OPTISOUND 3040 C 4wire EN
- OPTISOUND 3050C 4wire EN
- BM 100A ATEX EN
- BM 100A PROFIBUS PA EN
- BM 102 ATEX EN
- OPTISOUND 3040 Ex EN
- OPTISENS AAC 050 EN
- OPTISENS AAM 2080 EN
- OPTISENS AAS 2000 EN
- OPTISENS CAC 050 EN
- OPTISENS MAC 080 EN
- OPTISENS OAM 2080 EN
- OPTISENS OAS 2000 EN
- OPTISENS PAC 050 EN
- OPTISENS PAS 2000 EN
- H250 M40 NEPSI Ex d-Ex t
- H250 M40 NEPSI Ex ia
- H250 M40 NEPSI Ex nA
- DK 32-DK 34 NEPSI Ex i
- H250 M9 NEPSI Ex nA
- DK 32-DK 34 NEPSI Ex nA
- DK 37 NEPSI Ex i
- H250 M40 FOUNDATION FIELDBUS
- H250 M40 PROFIBUS PA
- ESKII HART
- GFC 300 FOUNDATION FIELDBUS
- GFC 300 Modbus
- UFC 030 PROFIBUS PA
- MFC 300 Modbus
- MFC 300 Profibus
- MFC 400 FOUNDATION FIELDBUS
- MFC 400 Modbus
- MFC 400 Profibus
- VFM 1091
- Summit 8800 Vol 1
- Summit 8800 Vol 2
- Summit 8800 Vol 3
- OPTIFLEX 1300C FOUNDATION FIELDBUS
- OPTIFLEX 1300C PROFIBUS PA
- OPTIFLEX 2200 cFMus
- PTIFLEX 2200 FOUNDATION FIELDBUS
- OPTIFLEX 2200 IECEX
- OPTIFLEX 2200 PROFIBUS
- OPTIWAVE 5200 PROFIBUS
- OPTIFLEX 2200C SIL
- OPTIFLEX Hart
- OPTIWAVE Hart
- OPTIFLEX 1300 IECEx
- BM 70 A-P
- OPTITEMP Compact sensors
- OPTISENS PH 8590
- OPTISENS PH 9500
- IFC 090 Converter FOUNDATION FIELDBUS
- ALTOFLUX 2W IFM 4042K
- IFC 010 Converter HART
- IFC 090 Converter HART
- IFC 090 Converter PROFIBUS
- OPTISONIC V6 Modbus
- BM 100 HART
- BM 102 HART
- BATCHCONTROL 5014 C
- BATCHFLUX 5500 C EN
- IFC 050 Converter EN
- IFC 100 Converter EN
- IFC 300 Converter EN
- IFC 300 Converter ES
- OPTIFLUX 1000 EN
- OPTIFLUX 2000 EN
- OPTIFLUX 4000 EN
- OPTIFLUX 5000 Flange EN
- OPTIFLUX 5000 Sandwich EN
- OPTIFLUX 6000 EN
- OPTIFLUX 7300 EN
- TIDALFLUX 2300 F Ex EN
- H250 M40 EN
- H250 M8-M9-M10 EN
- DK 32 Purge EN
- DK 32-DK 34-DK 37 EN
- DK 46-47-48-800 EN
- DK 46 I-DK 47 I EN
- DK 700 EN
- GA 24 EN
- H250 Reed MS14 EN
- VA 40 ATEX II2G Ex i EN
- VA FLOWMETERS EN
- ALTOSONIC III EN
- ALTOSONIC V EN
- ALTOSONIC V12 EN
- ALTOSONIC V Modbus EN
- UFC 400 FOUNDATION FIELDBUS EN
- UFC 400 Modbus EN
- UFM 3030 EEx EN
- UFM 800 Hot-Tap EN
- MFC 300 EN
- MFC 400 EN
- OPTIBATCH 4011 C EN
- OPTIGAS 4010 C EN
- OPTIMASS 1000 EN
- OPTIMASS 2000 EN
- OPTIMASS 3000 EN
- OPTIMASS 6000 EN
- OPTIMASS 7000 EN
- OPTIMASS with MFC 300 EN
- OPTIMASS Sensors Corrosion guidelines EN
- DW 181-182-183-184 EN
- DWM 1000-2000 EN
- OPTIFLEX 1100C EN
- OPTIFLEX 1300C EN
- OPTIFLEX 2200 C_F EN
- BM 26 A EN
- BM 26 BASIC_ADVANCED EN
- BM 500 EN
- BM 70 A_P EN
- BM 700 EN
- BM 702 EN
- BM 702 A EN
- BW 25 EN
- OPTIWAVE 7300 WHG Overfill Protection EN
- OPTIWAVE 6300C ATEX EN
- OPTIWAVE 7300C ATEX EN
- OPTIWAVE 8300C Marine ATEX EN
- LEM 300 EN
- LS 72xx EN
- TT 51 SERIES EN
- OPTIBAR DP 7060 C EN
- OPTIBAR P 1010 C EN
- OPTIBAR P 2010 C EN
- OPTIBAR P 3050 C EN
- OPTIBAR PC 5060 C EN
- ACM 500 EN
- SMARTSENS ORP 8150 Ex EN
- SMARTSENS PH 8xxx Ex EN
- C95 CI EN
- ALTOFLUX 2W IFM 4042K EN
- ALTOFLUX IFS 4000 EN
- ALTOFLUX M 900 EN
- AQUAFLUX EN
- BATCHFLUX 5015 K EN
- ECOFLUX IFS 1000 EN
- IFC 010 Converter EN
- IFC 020 Converter EN
- IFC 090 Converter EN
- IFC 110 Converter EN
- IFC 210 E EN
- OPTIFLUX 2070 EN
- H54 M4 EN
- GFM 700 EN
- OPTISONIC 7060 EN
- UFM 500 ATEX EN
- CORIMASS P Series EN
- CORIMASS G-MFM 4085 EN
- OPTIMASS with MFC 05x EN
- CORIMASS G-MFM 4085 EEx EN
- BM 100A EN
- BM 102 EN
- BM 90 EN
- LS 4100 EN
- LS 6500 EN
- LS 6600 EN
- M10 Converter HART 0201
- UFC 030 HART
- UFC 400 PROFIBUS PA-PROFIBUS DP
- MFC 010 C Converter
- OPTIMASS 2400
- DWM 2000 LCD
- BM 70 M
- CARGOMASTER
- OPTIWAVE 5200 cFMus
- OPTIWAVE 5200 FOUNDATION FIELDBUS
- OPTIWAVE 5200 IECEx
- OPTIWAVE 5200C SIL
- OPTIWAVE 6300 IECEx
- OPTIWAVE 6300C FOUNDATION FIELDBUS
- OPTIWAVE 6300C PROFIBUS PA
- OPTIWAVE 7300C FOUNDATION FIELDBUS
- OPTIWAVE 7300C PROFIBUS PA
- OPTIWAVE 7300 IECEx
- IFC 110 Converter
- IFC 110 Converter HART V0201
- UFC 500 HART
- BM 100A Handbook
- BM 102 Handbook