Advertising
background image

3.3.2 [I 0 PCT]

:

Program current output
at 0 %flow

Range: 00 mA

≤ [I 0 PCT] ≤ 16 mA

NOTE:

This value must be lower than the [I 100 PCT] value !!
If this is not the case, a PARAMERROR message will appear
during the parameter check procedure.

3.3.3 [I 100 PCT]

:

Program current output
at100% flow.

Range: 04 mA

≤ [I 100 PCT] ≤ 20 mA

[I 100 PCT] must exceed [I 0 PCT] by at least 4 mA; if this is
not the case, a PARAMERROR message appears during the
parameter check (see section D.4).

3.3.4 [I MAX]

:

Program maximum out
put current

The maximum output level can be limited to protect accesso-
ry equipment.

Range: 04 mA

≤ I MAX ≤ 22 mA

[I MAX] must be equal to or greater than [I 100 PCT]; if this is
not the case, a PARAMERROR message appears during the
parameter check (see section D.4).

3.3.5 T - CONST.I

:

Time constant of cur-
rent output

To flatten out sudden fluctuations in the current output signal
a first order filter is included.
Program the time constant for the current output:
Range: 4.0000 E-2

≤ T - CONST. ≤ 3.6000 E 3

Recommended initial value : 2 to 5 sec.

ATTENTION: Time constant also affects readings on

LC-display.