OPERATION

4

35

OPTIFLEX 2200 C

www.krohne.com

09/2013 - 4002573201 - AD FF OPTIFLEX 2200 R01 en

NORMAL

Normal

RW

This is the mode which the block should be set to during

normal operating conditions.

Auto

Setting:

Auto / OOS

ST_REV

ST_REV

ST_REV

ST_REV

Static Revision

Static Revision

Static Revision

Static Revision

R

The revision level of the static data associated with the

function block. The revision value will be incremented each

time a static parameter value in the block is changed.

0

Setting:

0...65535

STRATEGY

STRATEGY

STRATEGY

STRATEGY

Strategy

Strategy

Strategy

Strategy

RW

The strategy field can be used to identify grouping of blocks.

This data is not checked or processed by the block.

0

Setting:

0...65535

TAG_DESC

TAG_DESC

TAG_DESC

TAG_DESC

Tag Description

Tag Description

Tag Description

Tag Description

RW

This is the user description of the intended application of the

block.

blanks

Setting:

≤32 digits

ACK_OPTION

ACK_OPTION

ACK_OPTION

ACK_OPTION

Acknowledge Option

Acknowledge Option

Acknowledge Option

Acknowledge Option

RW

Selection of whether alarms associated with the function

block will be automatically acknowledged.

Uninitialized

Setting:

HiHi Alm Auto Ack / Hi Alm Auto Ack / LoLo Alm Auto Ack / Lo

Alm Auto Ack / Blk Alm Auto Ack / Fail Alm Auto Ack / Off

Spec Alm Auto Ack / Maint Alm Auto Ack / Check Alm Auto

Ack

ALARM_HYS

ALARM_HYS

ALARM_HYS

ALARM_HYS

Alarm Hysteresis

Alarm Hysteresis

Alarm Hysteresis

Alarm Hysteresis

RW

The amount by which the PV must return within the alarm

limits before the alarm condition clears. Alarm hysteresis is

expressed as a percentage of the PV span.

0.5

Setting:

0...50%

ALARM_SUM

ALARM_SUM

ALARM_SUM

ALARM_SUM

Alarm Summary

Alarm Summary

Alarm Summary

Alarm Summary

The current alert status, unacknowledged states, unreported

states and disabled states of the alarms associated with the

function block.

CURRENT

Current

R

The active status of each alarm.

Uninitialized

Setting:

HiHi Alarm / Hi Alarm / LoLo Alarm / Lo Alarm / Block Alarm

UNACKNOWLEDGED

Unacknowledged

R

The unacknowledged state of each alarm.

Uninitialized

Setting:

HiHi Alarm Unack / Hi Alarm Unack / LoLo Alarm Unack / Lo

Alarm Unack / Block Alarm Unack

UNREPORTED

Unreported

R

The unreported states of each alarm.

Uninitialized

Setting:

HiHi Alarm Unrep / Hi Alarm Unrep / LoLo Alarm Unrep / Lo

Alarm Unrep / Block Alarm Unrep

DISABLED

Disabled

R

The disabled state of each alarm

Uninitialized

Setting:

HiHi Alarm Disabled / Hi Alarm Disabled / LoLo Alarm

Disabled / Lo Alarm Disabled / Block Alarm Disabled

BLOCK_ALM

BLOCK_ALM

BLOCK_ALM

BLOCK_ALM

Block Alarm

Block Alarm

Block Alarm

Block Alarm

The block alarm is used for all configuration, hardware,

connection failure or system problems in the block. The cause

of the alert is entered in the subcode field. The first alert to

become active will set the "Active" status in the "Status"

attribute. As soon as the "Unreported" status is cleared by the

alert reporting task, another block alert may be reported

without clearing the "Active" status, if the subcode has

changed.

-

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value