LOW_CUT

LOW_CUT

LOW_CUT

LOW_CUT

Low Cutoff

Low Cutoff

Low Cutoff

Low Cutoff

RW

Limit used in square root processing. A value of zero percent

of scale is used in block processing if the transducer value

falls below this limit, in %of scale. This feature may be used to

eliminate noise near zero for a flow sensor.

0.0

Setting:

≥0.0

OUT

OUT

OUT

OUT

Output

Output

Output

Output

RW

The primary analogue discrete value calculated as a result of

executing the function.

STATUS

Status

R

Digital transducers, unlike their analogue versions, can detect

faults that make the measurement bad or prevent the

actuator from responding. This additional, valuable

information will be passed along with each transmission of a

data value in the form of a status attribute.

VALUE

Value

RW

A numerical quantity entered by a user or calculated by the

algorithm.

0.0

OUT_SCALE

OUT_SCALE

OUT_SCALE

OUT_SCALE

Output Scale

Output Scale

Output Scale

Output Scale

RW

The high and low scale values, engineering units code and

number of digits to the right of the decimal point to be used in

displaying the OUT parameter and parameters which have the

same scaling as OUT.

EU_100

EU at 100%

RW

The engineering unit value which represents the upper end of

range of the associated block parameter.

100.0

EU_0

EU at 0%

RW

The engineering unit value which represents the lower end of

range of the associated block parameter.

0.0

UNITS_INDEX

Units Index

RW

Device Description units code index for the engineering unit

descriptor for the associated block value.

Uninitialized

Setting:

All units are possible.

DECIMAL

Decimal

RW

The number of digits to the right of the decimal point which

should be used by an interface device in displaying the

specified parameter.

0

PV

PV

PV

PV

Process Value

Process Value

Process Value

Process Value

Either the primary analog value for use in executing the

function, or a process value associated with it. May also be

calculated from the RBACK value of an AO block.

-

STATUS

Status

R

Digital transducers, unlike their analogue versions, can detect

faults that make the measurement bad or prevent the

actuator from responding. This additional, valuable

information will be passed along with each transmission of a

data value in the form of a status attribute.

0

VALUE

Value

R

A numerical quantity entered by a user or calculated by the

algorithm.

0.0

PV_FTIME

PV_FTIME

PV_FTIME

PV_FTIME

Process Value Filter

Process Value Filter

Process Value Filter

Process Value Filter

Time

Time

Time

Time

RW

Time constant of a single exponential filter for the PV, in

seconds.

0.0

Setting:

0.0…60.0

SIMULATE

SIMULATE

SIMULATE

SIMULATE

Simulate

Simulate

Simulate

Simulate

Allows the transducer analog input or output to the block to be

manually supplied when simulate is enabled. When simulate

is disabled, the simulate value and status track the actual

value and status.

SIMUULATE_STATUS

Simulate Status

RW

Used for the transducer status when simulation is enabled.

0

SIMULATE_VALUE

Simulate Value

RW

Used for the transducer value when simulation is enabled.

0.0

Setting:

-3.39E38…+3.39E38 / -INF (-infinite) / + INF (+infinite)

TRANSDUCER_STATUS

Transducer Status

R

Status of value supplied by transducer.

0

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value