Operation – KROHNE PTIFLEX 2200 FOUNDATION FIELDBUS User Manual

Page 36

Advertising
background image

4

OPERATION

36

OPTIFLEX 2200 C

www.krohne.com

09/2013 - 4002573201 - AD FF OPTIFLEX 2200 R01 en

UNACKNOWLEDGED

Unacknowledged

RW

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

ALARM_STATE

Alarm State

R

A discrete enumeration which gives an indication of whether

the alert is active and whether it has been reported.

Uninitialized

Setting:

Uninitialized / Clear - reported / Clear - not reported / Active -

reported / Active - not reported

TIME_STAMP

Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received - even if another change of

state occurs.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

SUB_CODE

Subcode

R

An enumeration specifying the cause of the alert to be

reported.

Other

Setting:

Other / Block Configuration / Link Configuration / Simulation

Active / Local Override / Device Fault State / Device

Maintenance / Input Failure / Output Failure / Memory

Failure / Lost Static Data / Lost NV Data / Readback Check /

Maintenance Needed / Power Up / Out Of Service

VALUE

Value

R

The value of the associated parameter at the time the alert

was detected.

0

Setting:

0...255

CHANNEL

CHANNEL

CHANNEL

CHANNEL

Channel

Channel

Channel

Channel

RW

The number of the logical hardware channel that is connected

to this I/O block. This information defines the transducer to be

used going to or from the physical world.

0

Setting:

0. Uninitialized

1. Level

2. Distance

3. Conversion

4. Distance conversion

FIELD_VAL

FIELD_VAL

FIELD_VAL

FIELD_VAL

Field Value

Field Value

Field Value

Field Value

Raw value of the field device in percent of the PV range, with a

status reflecting the transducer condition, before signal

characterization (L_TYPE) or filtering (PV_FTIME).

STATUS

Status

R

Digital transducers, unlike their analogue versions, can detect

faults that make the measurement bad or prevent the

actuator from responding. This additional, valuable

information will be passed along with each transmission of a

data value in the form of a status attribute.

VALUE

Value

R

A numerical quantity entered by a user or calculated by the

algorithm.

0.0

GRANT_DENY

GRANT_DENY

GRANT_DENY

GRANT_DENY

Grant Deny

Grant Deny

Grant Deny

Grant Deny

Options for controlling access of host computers and local

control panels to operating, tuning and alarm parameters of

the block.

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value

Advertising