4 .2 electrical specifications – KROHNE Summit 8800 Vol 1 User Manual

Page 27

Advertising
background image

27

www.krohne.com

08/2013 - MA SUMMIT 8800 Vol1 R02 en

SUMMIT 8800

INSTALLATION AND REPLACEMENT

04

Figure 10 Cable assembly

4 .2 Electrical Specifications

4 .2 .1 Electrical Installation

The SUMMIT 8800 is certified to be in compliance with IEC 61010-1:2001 provided it is installed

in accordance with the instructions supplied.

The SUMMIT 8800 must be powered by:

A Class 2 power supply is defined by article 725.41 of the National Electrical Code (NEC Code

book) and has limited output power.

In addition the wiring between the SUMMIT 8800 and its power supply must be sufficiently rated

(10A) with a minimum cross section area of 1.5mm2 and PVC insulation. A suitable rated switch

or circuit breaker must be included to allow isolation of power supply to the SUMMIT 8800. The

device should be mounted as near to the equipment as practically possible.

No routine maintenance is required to ensure continuous operation; however, should a system

failure occur during operations, then the most likely cause of malfunction is that of a require-

ment not being fully or correctly implemented. If a fault or warning occurs, the cause should be

determined in a logical and systematic manner following the guide given below. All maintenance

tasks should be carried out by qualified personnel only.

Advertising