KROHNE Summit 8800 Vol 1 User Manual

Page 85

Advertising
background image

85

www.krohne.com

08/2013 - MA SUMMIT 8800 Vol1 R02 en

SUMMIT 8800

CALIBRATION

08

Main Controls:
Start Calibrate

starts the calibration process

Write

write the new calibration data to the connected flow computer

Discard

discards any calibration changes made.

Default

reverts to default factory calibration.

Stop calibrate

stops the calibration process.

Figure 93 Calibrate analog input

Adjusting the input range:

• Evaluate the field instrument data sheet and take particular note of its range setting for

minimum and maximum process values. Assume that a board arrives factory calibrated for 4

and 20mA. In below example a field temperature sensor ranges -50 to 150 degrees Celsius.

Alter the two wanted field record accordingly (as shown below). Do not click either of the SET

buttons but click the WRITE button.

Figure 94 Calibration selection screen

Advertising