Electrical connections – KROHNE MFC 300 EN User Manual

Page 56

Advertising
background image

4

ELECTRICAL CONNECTIONS

56

MFC 300

www.krohne.com

02/2012 - 4000498602 - MA MFC 300 R03 en

Pulse/frequency output passive, modular I/Os

• U

ext

≤ 32 VDC

• f

max

in the operating menu set to f

max

≤ 100 Hz:

I ≤ 100 mA
open:
I ≤ 0.05 mA at U

ext

= 32 VDC

closed:
U

0, max

= 0.2 V at I ≤ 10 mA

U

0, max

= 2 V at I ≤ 100 mA

• f

max

in operating menu set to 100 Hz < f

max

≤ 10 kHz:

open:
I ≤ 0.05 mA at U

ext

= 32 VDC

closed:
U

0, max

= 1.5 V at I ≤ 1 mA

U

0, max

=2.5 V at I ≤ 10 mA

U

0, max

= 5 V at I ≤ 20 mA

• If the following maximum load impedance R

L, max

is exceeded, the load impedance R

L

must

be reduced accordingly by parallel connection of R:
f ≤ 100 Hz: R

L, max

= 47 kΩ

f ≤ 1 kHz: R

L, max

= 10 kΩ

f ≤ 10 kHz: R

L, max

= 1 kΩ

• The minimum load impedance R

L, min

is calculated as follows:

R

L, min

= (U

ext

- U

0

) / I

max

• Can also be set as status output; refer to status output connection diagram.
• X designates the connection terminals A, B or D, depending on the version of the signal

converter.

INFORMATION!
For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).

Figure 4-21: Pulse frequency output passive P

p

.book Page 56 Monday, February 6, 2012 11:01 AM

Advertising