Installation and operating instructions BM 70 A/P

Page: 25

11/00

6.2 Ambient conditions

6.2.1 Hazardous locations

BM 70 A/P Ex is suitable for use in hazardous locations of the following zones: 0, 1, 2

Temperature classes: T6...T2; danger groups: IIA...IIC

For further information: see Section 10.

6.2.2 Ambient temperature of signal converter
BM 70 A/P with horn antenna or Wave-Guide:

-20 ... +55°C

(-4 ... +131°F)

A "BM 70 sunshade" should be fitted if the converter is located in the open with the likelihood of
strong insolation (see Section 6.1.9).

6.2.3 Flange temperature

Horn antenna, Wave-Guide (T

amb

*

50°C):

-30 ... +130°C

(-22 ... +266°F)

Horn antenna, Wave-Guide (T

amb

*

55°C):

-30 ... +120°C

(-22 ... +248°F)

High-temperature version with distance piece and

FFKM gasket (Kalrez 4079
or Parofluor V3819-75):

-30 ... +250°C ** (-22 ... +482°F)

Kalrez 2035 gasket:

-30 ... +210°C

(-22 ... +410°F)

Viton gasket:

-30 ... +200°C

(-22 ... +392°F)

FEP-sheathed gasket:

-30 ... +200°C

(-22 ... +392°F)

Wave-Stick, permanently:

-20 ... +100°C

(-4 ... +218°F)

Wave-Stick, pressure-dependent (see 6.3.5), with no mechanical

loading radial to the rod:

bis +150°C (302°F)

Wave-Stick, steam cleaning (CIP, SIP) for 30 minutes:

max. +160°C (320°F)

* Tamb is the ambient temperature of the signal converter
** Safety limit: +280°C (536°F)

6.2.4 Ambient temperature limits
Signal converter:
Measuring function OK, but LCD "freezes up":

min. - 40°C (-40°F)

Functional upper limit, for max. 2 hours:

max. +70°C (+158°F)

Flange system:
see Section 6.2.3

6.2.5 Storage temperature

-20 ... +60°C (-4 ... +140°F)

6.2.6 Environment class

Locations exposed direct to open-air climate, D1 Severity in conformity with EN 60654-1

6.2.7 Protection category

Signal converter:

IP 66 / IP 67 (equivalent to NEMA 6)