KROHNE BM 70 A_P EN User Manual
Page 41
Installation and operating instructions BM 70 A/P
Page: 41
11/00
Function (Fct.)
Enter range
Default value
Description
3.4
USER DATA
3.4.1 LANGUAGE
Options
GB/USA,
D, F, I, E, P, S
GB/USA *
Select language to be used in the display
(English, German, French, Italian, Spanish, Portu-
guese, Swedish)
3.4.2 ENTRY CODE 1
Options
NO
YES
NO
Switch the access lockout for the configuration menu
on/off.
3.4.3 CODE 1
Enter code
RRREEEUUU
Input of the Entry Code.
3.4.4 LOCATION
Text
BM70A-00
BM70P-00
Input of a max. 8-character device identifier.
3.5
APPLICAT.
3.5.1 AUTO TANKH.
Special function
Automatic determination of the tank height.
3.5.2 EMPTY.SPEC.
Options
OFF
ON
RECORD
OFF *
Switch the empty-tank spectrum (profile of the empty
tank) on/off, or make new recording.
3.5.3 TIMECONST.
Value
1 ... 100 [s] (BM 70 A)
10 ... 100 [s] (BM 70 P)
10 s (BM 70 A)
30 s (BM 70 P)
Input of the time constant for measured-value filtering
(low-pass).
3.5.4 TRACING.VEL.
Value
0.01 ... 10.00 [m/Min] (BM 70 A)
0.01 ... 1.00 [m/Min] (BM 70 P)
0.50 m/min
(BM 70 A)
0.10 m/min
(BM 70 P)
Input of the maximum rate of change in the level that
can occur in operation.
3.5.5 MULT.REFL.
Options
NO
YES
NO
Switch the multi-reflection identifier on/off.
3.5.6 BD-DETECT.
Options
NO
YES
YES
Switch the block distance (overfill) detector on/off.
3.5.7 FUNCT. FTB
Options
OFF
PARTIAL
FULL
OFF
Select function of the tank bottom tracking system.
(FULL for BM 70 A only)
3.5.8 EPSILON R
Enter
1.1000 ... 8.0000
2.0000
Input of the relative permittivity of the product for the
tank bottom tracking system.
3.5.9 TANKTYPE
Options
STORAGE TANK
PROC.TANK.
AGITATOR
PROC.TANK.
Select the tank type.
(AGITATOR for BM 70 A only)
3.6
SW.OUTP.S.
3.6.1 FUNCTION S
Options
OFF
LEVEL
DISTANCE
CONVERSION
REFLECTION
ERROR OPEN
ERROR CLOSED
ERROR OPEN
Select the function of the switching output.
3.6.2 TYPE S
Option
HIGH
LOW
HIGH
Select type of limit value for the switching output.
(not applicable to Function OFF, ERROR OPEN or
ERROR CLOSED)
3.6.3 THRESHOLD
Value
-200.00 ... +200.00 [m]
0.00 ... 99999.99 [m3]
0 ... 100 [Refl.]
5.00 m
5.00 m3
50
Input of the threshold value for the switching output.
(Input is dependent on the function of the switching
output. The values for level and distance include the
tank bottom and reference offset, resp.)
3.6.4 HYSTERESIS
Value
0.00 [m] ... Tank height
0.00 ... 99999.99 [m3]
0 ... 100 [Refl.]
0.10 m
0.10 m3
10
Input of the hysteresis for the switching output.
(Input is dependent on the function of the switching
output.)
*:
Default values following a parameter reset (use of a new EEPROM not yet described).
The factory setting for the parameters marked with * is dependent upon the device version and
customer specifications (if the tank height is known at the time the order is placed).