USER DATA

3.4.1 LANGUAGE

Options

GB/USA,

D, F, I, E, P, S

GB/USA *

Select language to be used in the display
(English, German, French, Italian, Spanish, Portu-
guese, Swedish)

3.4.2 ENTRY CODE 1

Options

NO

YES

NO

Switch the access lockout for the configuration menu
on/off.

3.4.3 CODE 1

Enter code

RRREEEUUU

Input of the Entry Code.

3.4.4 LOCATION

Text

BM70A-00
BM70P-00

Input of a max. 8-character device identifier.

3.5

APPLICAT.

3.5.1 AUTO TANKH.

Special function

Automatic determination of the tank height.

3.5.2 EMPTY.SPEC.

Options

OFF

ON

RECORD

OFF *

Switch the empty-tank spectrum (profile of the empty
tank) on/off, or make new recording.

3.5.3 TIMECONST.

Value

1 ... 100 [s] (BM 70 A)

10 ... 100 [s] (BM 70 P)

10 s (BM 70 A)
30 s (BM 70 P)

Input of the time constant for measured-value filtering
(low-pass).

3.5.4 TRACING.VEL.

Value

0.01 ... 10.00 [m/Min] (BM 70 A)
0.01 ... 1.00 [m/Min] (BM 70 P)

0.50 m/min
(BM 70 A)
0.10 m/min
(BM 70 P)

Input of the maximum rate of change in the level that
can occur in operation.

3.5.5 MULT.REFL.

Options

NO

YES

NO

Switch the multi-reflection identifier on/off.

3.5.6 BD-DETECT.

Options

NO

YES

YES

Switch the block distance (overfill) detector on/off.

3.5.7 FUNCT. FTB

Options

OFF

PARTIAL

FULL

OFF

Select function of the tank bottom tracking system.
(FULL for BM 70 A only)

3.5.8 EPSILON R

Enter

1.1000 ... 8.0000

2.0000

Input of the relative permittivity of the product for the
tank bottom tracking system.

3.5.9 TANKTYPE

Options

STORAGE TANK

PROC.TANK.

AGITATOR

PROC.TANK.

Select the tank type.
(AGITATOR for BM 70 A only)

3.6

SW.OUTP.S.

3.6.1 FUNCTION S

Options

OFF

LEVEL

DISTANCE

CONVERSION

REFLECTION

ERROR OPEN

ERROR CLOSED

ERROR OPEN

Select the function of the switching output.

3.6.2 TYPE S

Option

HIGH

LOW

HIGH

Select type of limit value for the switching output.
(not applicable to Function OFF, ERROR OPEN or
ERROR CLOSED)

3.6.3 THRESHOLD

Value

-200.00 ... +200.00 [m]

0.00 ... 99999.99 [m3]

0 ... 100 [Refl.]

5.00 m

5.00 m3
50

Input of the threshold value for the switching output.
(Input is dependent on the function of the switching
output. The values for level and distance include the
tank bottom and reference offset, resp.)

3.6.4 HYSTERESIS

Value

0.00 [m] ... Tank height

0.00 ... 99999.99 [m3]

0 ... 100 [Refl.]

0.10 m

0.10 m3
10

Input of the hysteresis for the switching output.
(Input is dependent on the function of the switching
output.)

*:

Default values following a parameter reset (use of a new EEPROM not yet described).
The factory setting for the parameters marked with * is dependent upon the device version and
customer specifications (if the tank height is known at the time the order is placed).

Advertising