Commissioning / operation – KROHNE UFC 400 PROFIBUS PA-PROFIBUS DP User Manual
Page 43
COMMISSIONING / OPERATION
4
43
UFC 400
www.krohne.com
05/2014 - 4003118502 - AD UFC 400 PROFIBUS R02 en
if condensed status and diagnosis
condensed status and diagnosis
condensed status and diagnosis
condensed status and diagnosis handling selected:
Above mentioned definitions for both diagnosis and status will be internally used for PROFIBUS
diagnosis and status handling of the classifications stated above which will be possible for the
variable "Event groups".
if classic status and diagnosis
classic status and diagnosis
classic status and diagnosis
classic status and diagnosis handling selected:
Above mentioned definitions for both diagnosis and status will be internally used for PROFIBUS
diagnosis and status handling of the classifications stated above which will be possible for the
variable "Event groups".
If using the Display Menu
Display Menu
Display Menu
Display Menu of the UFC 400 please have a look at the general description of menu
section C1.10.3 to C1.10.8 located at the end of this documentation.
"F"
Failure
diagnosis: DIA_MAINTENANCE_ALARM (Maintenance alarm (40))
status: BAD - maintenance alarm
"S"
Out of specification
diagnosis: DIA_MAINTENANCE_DEMAND (Maintenance demanded (41))
status: UNCERTAIN - process related, no maintenance
"M"
Maintenance required
diagnosis: DIA_MAINTENANCE (Maintenance required (37))
status: GOOD - maintenance demanded
"C"
Function check
diagnosis: DIA_FUNCTION_CHECK (Function check (42))
status: GOOD - function check
"I"
Information
diagnosis: NO DIAGNOSIS EVENTS (no diagnosis events)
1
status: GOOD - ok
1 Bit "EXTENSION_AVAILABLE" of parameter DIAGNOSIS will be set if at least one Bit of parameter "DIAGNOSIS_EXTENSION" has been
set.
"F"
Failure
diagnosis: DIA_HW_ELECTR (Hardware failure electronics (24))
status: BAD - Device Failure
"S"
Out of specification
diagnosis: DIA_MEASUREMENT (Measurement failure (29))
status: UNCERTAIN - sensor conver. not accur.
"M"
Maintenance required
diagnosis: DIA_MAINTENANCE (Maintenance required (37))
status: GOOD (NC) - maintenance required
"C"
Function check
diagnosis: NO DIAGNOSIS EVENTS (Status OK – function check only)
status: UNCERTAIN - simulated value (Function Check)
"I"
Information
diagnosis: NO DIAGNOSIS EVENTS (no diagnosis events)
1
status: GOOD - ok
1 Bit "EXTENSION_AVAILABLE" of parameter DIAGNOSIS will be set if at least one Bit of parameter "DIAGNOSIS_EXTENSION" has been
set.
CAUTION!
Only the classification of an above mentioned "Event groups" will be changeable
–
changing the
classification of a "Single event" is not possible at all!!