COMMISSIONING / OPERATION

4

43

UFC 400

www.krohne.com

05/2014 - 4003118502 - AD UFC 400 PROFIBUS R02 en

if condensed status and diagnosis

condensed status and diagnosis

condensed status and diagnosis

condensed status and diagnosis handling selected:

Above mentioned definitions for both diagnosis and status will be internally used for PROFIBUS
diagnosis and status handling of the classifications stated above which will be possible for the
variable "Event groups".

if classic status and diagnosis

classic status and diagnosis

classic status and diagnosis

classic status and diagnosis handling selected:

Above mentioned definitions for both diagnosis and status will be internally used for PROFIBUS
diagnosis and status handling of the classifications stated above which will be possible for the
variable "Event groups".

If using the Display Menu

Display Menu

Display Menu

Display Menu of the UFC 400 please have a look at the general description of menu

section C1.10.3 to C1.10.8 located at the end of this documentation.

"F"

Failure

diagnosis: DIA_MAINTENANCE_ALARM (Maintenance alarm (40))

status: BAD - maintenance alarm

"S"

Out of specification

diagnosis: DIA_MAINTENANCE_DEMAND (Maintenance demanded (41))

status: UNCERTAIN - process related, no maintenance

"M"

Maintenance required

diagnosis: DIA_MAINTENANCE (Maintenance required (37))

status: GOOD - maintenance demanded

"C"

Function check

diagnosis: DIA_FUNCTION_CHECK (Function check (42))

status: GOOD - function check

"I"

Information

diagnosis: NO DIAGNOSIS EVENTS (no diagnosis events)

1

status: GOOD - ok

1 Bit "EXTENSION_AVAILABLE" of parameter DIAGNOSIS will be set if at least one Bit of parameter "DIAGNOSIS_EXTENSION" has been

set.

"F"

Failure

diagnosis: DIA_HW_ELECTR (Hardware failure electronics (24))

status: BAD - Device Failure

"S"

Out of specification

diagnosis: DIA_MEASUREMENT (Measurement failure (29))

status: UNCERTAIN - sensor conver. not accur.

"M"

Maintenance required

diagnosis: DIA_MAINTENANCE (Maintenance required (37))

status: GOOD (NC) - maintenance required

"C"

Function check

diagnosis: NO DIAGNOSIS EVENTS (Status OK – function check only)

status: UNCERTAIN - simulated value (Function Check)

"I"

Information

diagnosis: NO DIAGNOSIS EVENTS (no diagnosis events)

1

status: GOOD - ok

1 Bit "EXTENSION_AVAILABLE" of parameter DIAGNOSIS will be set if at least one Bit of parameter "DIAGNOSIS_EXTENSION" has been

set.

CAUTION!
Only the classification of an above mentioned "Event groups" will be changeable

changing the

classification of a "Single event" is not possible at all!!