PROFIBUS SETTINGS

5

45

UFC 400

www.krohne.com

05/2014 - 4003118502 - AD UFC 400 PROFIBUS R02 en

Detailed description of special settings concerning the PROFIBUS features easily operated via
the local display menu of the signal converter (refer to the following sections). For a detailed
description of the menus and functions in general please refer to the standard product
documentation of the signal converter.

5.1 Menu A, Quick Setup

5.2 Menu B, Test

No.

Function

Setting / Description

A2 Tag

A2

Tag

Tag descriptor of the physical block of the PROFIBUS module will be

displayed. The Tag descriptor provides an application specific reference to

the blocks. It will be assigned by the user of the device. The Tag descriptor is

an octet string (a visible string will be preferred) consisting of 32 byte. The

first 21 characters will be displayed only!

A3 Reset

A3

Reset

A3.1

Reset Errors

Reset Errors? Select: no/yes

The following reset menus for the Totalisers are available only if the "quick access" has been activated in the menu

"Setup → Device → Quick Setup (C5.9.x)". Each Totaliser can be activated independently for quick access.

A3.2

FB3 Totaliser 1

Reset Totaliser 1 only? Select: No / Yes (available if activated in C5.9.1)

A3.3

FB4 Totaliser 2

Reset Totaliser 2 only? Select: No / Yes (available if activated in C5.9.2)

A3.4

FB5 Totaliser 3

Reset Totaliser 3 only? Select: No / Yes (available if activated in C5.9.3)

A4 Station Address

A4

Station Address

Selects the address of the device at the PROFIBUS interface.

The PROFIBUS address can also be changed using the PROFIBUS service

"set_slave_add". The input range is 0...125 according to the PROFIBUS

specification. Address 126 is the default address and cannot be set via the

PROFIBUS service "set_slave_add" - use menu instead to reset to default

address.

No.

Function

Settings / descriptions

B3 Information

B3.7

PROFIBUS

Available if there is a PROFIBUS interface in existence; the below mentioned

information will be displayed about the PROFIBUS interface:

Hardware Revision of the PROFIBUS interface used

Software Version of the PROFIBUS interface used

Date of Compilation