Specifications 113

4600 at 200V to 240V AC input

Power supply output

Rated steady-state power

800 W at 100V AC input

900 W at 120V AC input

1200 W at 200V to 240V AC

input

Maximum peak power

800 W at 100V AC input

900 W at 120V AC input

1200 W at 200V to 240V AC
input

HP 1200 W CS -48Vdc Power Supply specifications

Specification

Value

Input requirements

Rated input voltage

-36V to -72V DC

-48V DC, nominal input

Rated input frequency

Not applicable

Rated input current

38A at -36V DC

19A at -72V DC

28A at -48V DC, nominal input

Rated input power

1380 W at -36V DC input

1365 W at -72V DC input

1350 W at -48V DC, nominal
input

BTUs per hour

4713 at -36V DC input

4662 at -72V DC input

4610 at -48V DC, nominal input

Power supply output

Rated steady-state power

1200 W

Rated peak power

1200 W

CAUTION:

This equipment is designed to permit the connection of the earthed conductor of the

DC supply circuit to the earthing conductor at the equipment. See installation instructions.

CAUTION:

This equipment is designed to permit the connection of the earthed conductor of the

DC supply circuit to the earthing conductor at the equipment.

If this connection is made, all of the following must be met:

This equipment should be connected directly to the DC supply system earthing electrode
conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC supply

system earthing electrode conductor is connected.

This equipment should be located in the same immediate area (such as adjacent cabinets) as

any other equipment that has a connection between the earthed conductor of the same DC
supply circuit and the earthing conductor, and also the the point of earthing of the DC system.

The DC system should be earthed elsewhere.