Reducing Motor Noise or Leakage Current (n080)

Frequency setting varies according to inverter capacity (kVA).

(1) Reduce continuous output current when changing carrier frequency to

4 (10kHz) for the 200V class (1.5 W or more) and 400V class invert-
ers. Refer to the table above for the reduced current.

[Operation Condition]

•Input power supply voltage : 3-phase 200 to 230 V (200V class)

Single-Phase 200 to 240V (200V class)

3-Phase 380 to 460V (400V class)

•Ambient temperature: 14 to 122ºF (-10 to +50ºC)

(Protection structure: open chassis type

IP20)

(2) If the wiring distance is long, reduce the inverter carrier frequency as

described below

Voltage Class (V)

Capacity

(kW)

Initial Setting

Maximum

Continuous

Output Current

(A)

Reduced

Current (A)

Setting

Carrier

Frequency

200

Single-phase 3-

phase

0.1

4

10kHz

0.8

0.2 4

10kHz

1.6

0.4 4

10kHz

3.0

0.7 4

10kHz

5.0

1.5

3

7.5kHz

8.0

7.0

2.2

3

7.5kHz

11.0

10.0

3.7

3

7.5kHz

17.5

16.5

5.5

3

7.5kHz

25

23

7.5

3

7.5kHz

33

30

400

3-phase

0.2

3

7.5kHz

1.2

1.0

0.4

3

7.5kHz

1.8

1.6

0.7

3

7.5kHz

3.4

3.0

1.5

3

7.5kHz

4.8

4.0

2.2

3

7.5kHz

5.5

4.8

3.0

3

7.5kHz

7.2

6.3

3.7

3

7.5kHz

8.6

8.1

5.5

3

7.5kHz

14.8

*

7.5

3

7.5kHz

18

17

Wiring Distance between

Inverter and Motor

Up to 50m

Up to 100m

More than 100m

Carrier frequency

(n080 setting)

10kHz or less

(n080=1, 2, 3, 4, 7, 8, 9)

5kHz or less

(n080=1, 2, 7, 8, 9)

2.5kHz or less

(n080=1, 7, 8, 9,)