Building Interface Circuits with External Devices

Multi-function input terminal S1 to S7 functions can be changed when necessary by
setting parameters n051 or n052 respectively. The same value cannot be set to different
parameter settings.

* Numbers 1 to 7 are displayed in

G corresponding to the terminal number S1 to S7 respectively.

Using input signals

Setting

Name

Description

Ref.

0

FWD/REV run command

(3 wire sequence selection)

Setting enabled only for n052

74

1

Forward run

(2 wire sequence selection)

45

2

Reverse run

(2 wire sequence selection)

45

3

External fault (NO contact input)

Inverter stops by external fault signal input

Digital operator display is

“EF D “

.*

4

External fault (NC contact input)

5

Fault Reset

Resets the fault. Fault reset not

effective with the run signal ON.

50

6

Multi-step speed reference 1

50

7

Multi-step speed reference 2

50

8

Multi-step speed reference 3

50

9

Multi-step speed reference 4

50

10

JOG command

51

11

Accel/Decel time select

54

12

External baseblock

(NO contact input)

Motor coast to a stop by this

signal input.

Digital operator display is

“bb”.

13

External baseblock

(NC contact input)

14

Search command from

maximum frequency

Speed search

reference signal

63

15

Search command from

set frequency

63

16

Accel/decel hold command

64

17

LOCAL/REMOTE selection

46

18

Communication/control circuit

terminal selection

78

19

Emergency stop fault

(NO contact input)

Inverter stops by emergency stop signal input
according to stopping method selection (n005).
When frequency coasting to a stop (n005 is set
to 1) method is selected, inverter coasts to a
stop according to decel time setting 2 (n022).

Digital operator display is

sRp

(lit at fault, blinking at alarm).

20

Emergency stop alarm

(NO contact input)

21

Emergency stop fault

(NC contact input)

22

Emergency stop alarm

(NC contact input)

23

PID Control cancel

114

24

PID integral reset

114

26

Inverter overheat prediction OH3

“ “ (Blinking) is displayed on the
digital operator by signal input

25

PID intregal hold

114

34

UP/DOWN command

Setting enabled only for

n056 (terminal S7)

75

35

Self-test

Setting enabled only for

n056 (terminal S7)

114