Standard accessories, Accessories, Order details – JUMO 709050 IPC IGBT Power Converter Data Sheet User Manual
Page 12
JUMO GmbH & Co. KG • 36035 Fulda, Germany
2009-11-01/00389005
Data Sheet 70.9050
Seite 12/12
Standard accessories
1 Operating Manual
Accessories
Chokes
L = 0.6 mH / I
Nom
=75A, 100A or 200A
EMC filter (for voltage supply to the power section)
115V/250V/440V AC I
Nom
=16A, 20A, 32A, 63A or 100A,
EMC filter (for voltage supply to the control section)
115V/250V AC I
Nom
=1A
Semiconductor fuse (2 fuses required)
extra fast 200A for I
Nom
= 100A,
The I
2
t value of the semiconductor fuse must be smaller than 20000 A
2
s!
(only use for type 709050/X2... and 709050/X3... !)
Order details:
(1) Basic version
709050/81
IGBT power converter 70A (max. load voltage 120V) standard version
709050/91
Customer-specific version
709050/82
IGBT power converter 70A or 100A (max. load voltage 380V) standard version
709050/92
Customer-specific version
709050/83
IGBT power converter 200A (max. load voltage 210V) standard version
709050/93
Customer-specific version
(2) Voltage supply to the control section
x
x
x
11
115V AC +15/-20%, 48 ... 63Hz (only for 115V AC in the power section)
x x
x x
x x
12
230V AC +15/-20%, 48 ... 63Hz
(3)
Voltage supply to power section
x
x
x
115
115V AC +15/-20%, 48 ... 63Hz
x
x
x
230
230V AC +15/-20%, 48 ... 63Hz
x
x
x
400
400V AC +15/-20%, 48 ... 63Hz
(4) Load voltage
x x x x x x x x x
020
20V DC
x x x x x x x x x
060
60V DC
x x x x x x
x x
090
90V DC
x x
x x
x x
120
120V DC
x x
x
150
150V DC
x x
x
210
210V DC
x
270
270V DC
x
380
380V DC
(5) Load current
x x x x x x
070
70A DC
x x x
100
100A DC
x x x
200
200A DC
(6) Extra code for fault signal output
x x x x x x x x x
252
Relay SPDT (changeover contact) 3A
x x x x x x x x x
257
Optocoupler
(1)
(2)
(3)
(4)
(5)
(6)
Order code
-
-
-
-
-
Order example
709050/81
-
12
-
230
-
060
-
070
/
252