Technical data – JUMO 709050 IPC IGBT Power Converter Data Sheet User Manual

Page 2

Advertising
background image

JUMO GmbH & Co. KG • 36035 Fulda, Germany

2009-11-01/00389005

Data Sheet 70.9050

Seite 2/12

Technical data

Control

Voltage supply

Control signal

0(4) … 20mA

R

i

= 50

0(2) … 10V

R

i

= 25k

0(1) … 5V

R

i

= 12 k

Ω Manual control through an external 5 kΩ potentiometer

Input signal attenuation

Adjustment range 100 … 20%

Base load setting

0 ... 100%

Type 709050/X1...

Type 709050/X2...

Type 709050/X3...

Voltage supply
Control section

115V AC +15%/ -20%, 48 ... 63Hz, (only with 115V AC in the power section)

230V AC+15%/ -20%, 48 … 63Hz

Voltage supply
Power section

115V AC +15%/ -20%,48 ... 63Hz, 230V AC +15%/ -20%, 48 … 63Hz

400V AC +15%/ -20%,48 … 63Hz

Load voltage U

L rms

20V DC, 60V, 90V, 120V

20V DC, 60V, 90V, 120V, 150V, 210V,

270V, 380V

20V DC, 60V, 90V, 120V, 150V,

210V

Further voltages upon request

Load current U

L rms

DC 70A

DC 70A / 100A

DC 200A

Load type

Resistive loads

General characteristics

Circuit variants

Single-phase operation

Operating modes

Amplitude control

Subordinate control loop

As standard: free choice between U

2

-, P-, I

2

control via internal switches

Current limiting

In operation, the load current can be set in the range of 10 … 100% I

N

by a trimmer on the front panel.

This limits the rms-value of the load current.

Partial load failure

20 ... 100% of nominal current

R-control

-

Adjustment range from R

Nom

to 10x R

Nom

R

Nom

=

nominal voltage / nominal current

SIC reserve

-

Message indicated when the voltage reserve for SIC heating rods is exhaust-

ed

Actual value output

As standard: free choice between U

2

-, P-, or I

2

signal via internal switches,

adjustable 0 … 5V to 0 … 10V , I

max

∪ 2mA, offset deviation ≤ ± 5%

Control accuracy

The regulation will eliminate supply voltage variations within the tolerance range (+15%/ -20%) with an

accuracy of ± 0.5%

Electrical connection

Control leads via plug-in screw terminals for conductor cross sections 0.5 … 2.5mm

2

in the power section via cable lugs as

per DIN 46212

in the power section via 10mm

2

...

50mm

2

screw terminals

Power section via 10mm

2

... 95mm

2

screw terminals

Semiconductor fuse

The I

2

t value of an external fuse must

be smaller than 2000 A

2

s!

The I

2

t value of the integrated semiconductor fuse must be smaller than

20000 A

2

s!

Degree of protection

IP 00 as per EN 60 529

IP 10 as per EN 60 529

Protection class

Protection class I, with isolated control circuitry for connection to SELV circuits

Permissible ambient
temperature range

5 … 40°C (3K3 as per EN 60 721-3-3)

Permissible storage
temperature range

-10 … +70°C (1K3 as per EN 60 721-3-1)

Cooling

forced convection, maximum inlet air temperature 35°C

Climatic conditions

Rel. humidity

≤ 5 ... 85 % annual average, no condensation 3K3 as per EN 60 721

mounting position

vertical

Operating conditions

The converter is designed as a built-in device as per EN 50 178, pollution degree 2,

overvoltage category Ü III

Electromagnetic
compatibility

as per DIN 61326 emitted interference: Class A - Only for industrial use -

interference immunity: to industrial requirements

Test voltage

as per EN 50178

Creepage distances

Control section to load circuit

÷ 5.5 mm, control section to housing ÷ 5.5 mm, device can be connected to SELV

circuits. SELV = Separate Extra Low Voltage (safe low voltage)

Ground leakage current

The Ground leakage current of the IPC power converter used with an EMC filter in the supply cable is less than 3

mA (excluding any leakage current in the load).

Housing

Metal housing

Power consumption
of the control section

approx. 50VA

max. 100 VA

Standard accessories

1 operating manual B 70.9050.0...

Advertising