2 fieldbus status displays, Fieldbus status displays ( 86), Fieldbus status displays – Lenze E84AYCPM User Manual
Page 86: 11 diagnostics

Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
86
11
Diagnostics
11.1
LED status displays
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.1.2
Fieldbus status displays
The LEDs BS and BE indicate the fieldbus status.
[11-2] LED status displays BS and BE
E84YCPM006
BE
BS
LED
Colour
State
Description
BS
Green
Off
The communication module is not active on the fieldbus or is being
initialised.
Blinking
The communication module is in the DATA_EXCH state
("Data_Exchange"). Data are exchanged via PROFIBUS.
BE
Red
Blinking
Incorrect setting for the station address.
The communication module is initialised and internally operates with
the respective default values.
On
Bus error/fault is active (e.g. bus cable unplugged).
200 ms
200 ms
200 ms
200 ms